Table 4. Analog Outputs
Channel
Point
Signal Type
Number
AO 1
Analog
41
LEDs
The U141v+ modules have diagnostic LEDs to
assist troubleshooting.
Table 5. Run LED
Status
Meaning
2 times per second
Normal operation.
5 times per second
Transferring firmware.
Once every 2 seconds
Auto-detecting baud rate.
Table 6. Error LED
Status
Meaning
2 times per second
Firmware error. Transfer
memory to the module to
correct.
Solid on
Hardware failure.
Table 7. CW LED
Status
Meaning
Solid on
Motor is turning clockwise.
Blinking
Actuator motor hit end-of-
travel.
Table 8. CCW LED
Status
Meaning
Solid on
Motor is turning counter-
clockwise.
Blinking
Actuator motor hit end-of-
travel.
Power - On when the module is on.
Rx - On when the module receives data.
Tx - On when the module transmits data.
DO1 - On when digital output 1 is active.
CW - On when actuator motor turns
clockwise.
Revised 8/14/02 • U141v+
Range
Offset
Gain
0 to 10VDC
0.00
0.0625
CCW - On when actuator motor turns
counterclockwise.
Production Date
To determine when a module was
manufactured, check the module status
report for the module in WebCTRL or
SuperVision. Refer to the appropriate user's
guide for more information about the module
status report.
A sticker on the back of the module also
shows the date the module was
manufactured. The first three characters on
the sticker indicate the type of module. The
next two characters show the year and month
of manufacture. (The month digit is in
hexadecimal.)
11