Table 1 for information about wire length,
gauge, and shielding. Make sure the U141v+'s
power is off before wiring any inputs or
outputs.
• Thermistor: Precon type 2 (10kohm at
77°F). Input voltages should range
between 0.489V and 3.825V for
thermistors.
• 0 to 5VDC: When using 0 to 5VDC
signals, remove the pull up jumpers of
the U141v+. The pull up jumpers are
located behind the input port. You must
remove the cover to access the pull up
jumpers. The output impedance of a 0
to 5VDC source must not exceed
10kohms. The input impedance of the
U141v+ is approximately 1Mohm.
• Dry Contact: A 5VDC wetting voltage is
used to detect contact position. This
results in a 0.5mA maximum sense
current when the contacts are closed.
Table 1. Input Wiring Restrictions
Maximum
Input
Length
Universal
50 feet
15 meters
LogiStat
100 feet
Sensors
30 meters
No pulse accumulation inputs are allowed in
U141v+ FBs, except for the override button on
the LogiStat.

Using the LogiStat

Use Figure 10 and Figure 11 on page 8 to wire
a LogiStat, LogiStat Plus, or LogiStat Pro to
the U141v+.
Automated Logic Corporation recommends a
specific wire to connect the U141v+ to the
LogiStat. This 22AWG solid copper wire is
available from Magnum Cable Corporation,
Revised 8/14/02 • U141v+
Minimum
Gauge
Shielding
24AWG
shielded and
grounded to
module's "-"
or Gnd
terminal
22AWG
unshielded
U module
LogiStat
LS5v
4
Sw
3
Temp
2
Gnd
1
Figure 10. Connecting the LogiStat to the
Strip 1/4 inch off the ends of the wires before
connecting.
1. Insert wire
into opening
Figure 11. Flip Lever Wiring
Refer to the section "Writing GFBs for the
U141v+" on page 9 for more information
about using a LogiStat sensor.

Digital Output Wiring

The U141v+ has one digital output that can be
connected to a maximum of 24 Volts AC/DC
(see Figure 12). Each output is a dry contact
(rated at 1A maximum) that is configured as
normally open.
DO-2
DO-1
BUSS
Figure 12. Digital Output Wiring
Be sure the module's power is off before
connecting any inputs or outputs.
8
© 2002 Automated Logic Corporation
LogiStat
1 2 3 4
U141v+
2. Press black
tab down to
connect wire
DO
DO
Gnd
24VAC
+