Emergi-Lite Lux-Ray LED Podręcznik
Przeglądaj online lub pobierz pdf Podręcznik dla Sprzęt oświetleniowy Emergi-Lite Lux-Ray LED. Emergi-Lite Lux-Ray LED 2 stron. Emergency lighting
Również dla Emergi-Lite Lux-Ray LED: Podręcznik (2 strony)
Lux-Ray LED - Emergency lighting
WARNING:
Risk of Shock.
Disconnect Power before Installation.
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should
always be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1.
All servicing should be performed by qualified service personnel.
2.
All unused wires must be capped to prevent shorting.
3.
Do not let power supply cords touch hot surfaces.
4.
Do not mount near gas or electric heaters.
5.
Use caution when handling batteries.
6.
Equipment should be mounted in locations and at heights where it
will not readily be subjected to tampering by unauthorized
personnel.
7.
The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
8.
Do not use this equipment for other than intended use.
9.
Unit to be installed only as per configuration described in this
instruction manual.
SAVE THESE INSTRUCTIONS
Installation Instructions
Install fixture/lamp type combination no
higher than the maximum mounting heights
as stipulated in the "Lamp Mounting Height
IMPORTANT:
Cross-reference Table" (P/N 750.1924).
Refer to "Technical Infomation" section of
our website.
1. Turn off the building emergency circuit and the breaker of the AC cir-
cuit for normal lighting.
2. Remove the back plate from the package.
3. Open the inside cover by turning it. Identify the wires by using the
labels attached to them.
4. Choose the proper mounting below and continue to step 5.
Junction box mounting (Figure 1)
Knockout the desired holes in the back plate. Make the electrical
connections as shown in point 5. Route the wire connectors through
the large knockout and mount the back plate to the junction box.
Junction box
not supplied
Install ground
wire here
Pin guide
Figure 1
Emergi-Lite®
Tel: (888) 552-6467
®
Back plate
Inside cover
Fax: (800) 316-4515
Lux-Ray LED - Emergency lighting
Conduit entry mounting (Figure 2)
Remove plug on the back plate and knock out the desired holes in
the back plate to secure the unit on the wall. Install the conduit and
supply wires. For wet location: install a liquidtight™ fitting with teflon
tape. Use wire nuts provided with the unit. Bigger wire nuts might
interfere with internal components.
5. Electrical connections
See wiring diagrams below according to model ordered.
Red
White
(Positive DC)
(Neutral)
Blue
Black
(Negative DC)
(120 Vac)
Green
Green
Orange
(Ground)
(Ground)
(277 Vac)
(ACDC)
(SD) and (AC)
Connect ground wire.
Emergency Lighting connection:
Connect the neutral (white) wire.
120Vac connect black wire or
277Vac connect orange wire.
Normal Lighting connection:
Connect the neutral (white) wire.
120Vac connect black wire
277Vac connect orange wire.
Cap the unused wires separately.
Both emergency and
normal lighting must
have the same
IMPORTANT:
voltage value:
120/120Vac or
277/277Vac.
(ACSD and 2AC)
Black
(120 Vac)
OR
Orange
2 White
(277 Vac)
Wires
Wires To Be Attached
(Neutral)
Together
Green
(Ground)
(SD-CW)
www.emergi-lite.com
White
(Neutral)
Black
Red
(120 Vac)
(Positive DC)
Orange
Green
Blue
(277 Vac)
(Ground)
(Negative DC)
(DC)
Normal
Emergency
Lighting
Lighting
White (Neutral)
White (Neutral)
Black (120 Vac)
Black (120 Vac)
Orange (277 Vac)
Orange (277 Vac)
Green
(Ground)
Black
(120 Vac)
OR
Orange
(277 Vac)
Wires To Be Caped
Separately
Cold weather (option: -
CW): separate input wire
for the battery charger
and heating circuit.
Connect ground wire.
Connect white wires
(neutral) together.
Connect line voltage
wires together as shown
above wires. Cap the
unused wires
separately.
02/18 750.1712 Rev. D
1/2