Emergi-Lite EMIU-250W Instrukcja obsługi - Strona 7

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Falownik Emergi-Lite EMIU-250W. Emergi-Lite EMIU-250W 12 stron. Mini inverter

FIGURE 2C
WIRING DIAGRAM:
UN-SWITCHED
NORMALLY ON LOAD
120Vac
(Un-Switched)
Neutral
(see note 4)
Line 120Vac
120V
Neutral
(see note 4)
Ground
FIGURE 2D
WIRING DIAGRAM:
UN-SWITCHED
NORMALLY ON LOAD
WITH LCO.
(REFER TO FIGURE 6)
120Vac
(Un-Switched)
Neutral
(see note 4)
Line 120Vac
120V
Neutral
(see note 4)
Ground
Emergi-Lite®
Tel: (888) 552-6467
®
Input Wiring
Un-Switched Line
Neutral
Ground
(see note 3)
Primary
Un-Switched
AC Input
Normally ON
Lighting Load
Input Wiring
Un-Switched Line
Neutral
Ground
0-10V
Lighting Control
(see note 3)
Primary
Un-Switched
AC Input
Normally ON
Lighting Load
Fax: (800) 316-4515
Switched Line
Notes:
1. Connect fixture supply and unit ground in accordance with local and national
codes.
2. Single voltage wiring. Either 120V or 277V. Input and output voltage must be
the same.
3. Unit jumper wire is preset for 120Vac. If the unit is to be wired for 277Vac,
remove the jumper wire from the 120Vac INPUT POWER terminals and
reinstall the jumper wire into the 277Vac INPUT POWER terminals.
4. DO NOT COMBINE THE INPUT POWER NEUTRAL WITH THE LOAD
NEUTRAL.
Switched Line
LCO
LCO
Wire
Wire
Notes:
1. Connect fixture supply and unit ground in accordance with local and national
codes.
2. Single voltage wiring. Either 120V or 277V. Input and output voltage must be
the same.
3. Unit jumper wire is preset for 120Vac. If the unit is to be wired for 277Vac,
remove the jumper wire from the 120Vac INPUT POWER terminals and
reinstall the jumper wire into the 277Vac INPUT POWER terminals.
4. DO NOT COMBINE THE INPUT POWER NEUTRAL WITH THE LOAD
NEUTRAL.
www.emergi-lite.com
EMIU 125/250/400W Mini Inverter
Output Wiring
Line
Neutral
Lighting Load
Fluorescent, LED,
Incandescent
Output Wiring
Line
Neutral
Lighting Load
Fluorescent, LED,
Incandescent
0-10V
Wires to connect to
the Ballast / Driver
06/18 750.1782 Rev. J
7/12