How to Interlock Two VF Series Controls together
1. Remove the run jumper from TB2 terminals 8 & 9 of the subordinate control.
2. Add a wire from term. TB2-1 of the master control to terminal 7 of the subordinate control.
3. Add a wire from TB2-2 of the master control to terminal 8 of the subordinate control.
How to Interlock an FC-40 Plus Series to a VF Series Control
1. Add a wire from term. TB2-1 of the VF master control to TB2-11 of the
subordinate control.
2. Add a wire from TB2-2 of the VF master control to TB2-12 of the
subordinate control.
3. Move the run jumper on the subordinate control from TB2-6 & TB2-7 to
TB2-5 & TB2-6.
How to Interlock an FC-200 Series to a VF Series Control
1. Remove the RUN jumper from TB2- 8 & 9 of the subordinate control.
2. Add a wire from term. TB2-1 of the VF master control to TB2-7 of the
subordinate control.
3. Add a wire from TB2-2 of the VF master control to TB2-8 of the
subordinate control.
.