C - Compute and Compare Overall Current Draw
Calculate the total current draw for all door peripherals, all Hi-O interface devices, and all Hi-O enabled readers with the
following equation, adding terms as required.
I
= I
total
For this example, the total current draw is shown.
I
@ +12VDC = 15mA + 300mA + 28mA + 70mA + 160mA* + 40mA* = 613mA
total
I
@ +24VDC = 15mA + 150mA + 38mA + 70mA + 160mA*+ 40mA* = 473mA
total
* Notes:
a. The EDM-M draws 40mA standby current.
b. The Hi-O iCLASS reader requires a +24VDC to +12VDC converter module (EDGE EVO Hi-O Voltage Module
Compare the required current draw (I
1) to select the EH400 power scheme. The CAN DC PWR Output represents the entire power output capacity of the
EH400.
Device
Hi-O Networked Controller
(EH400)
In this example, the EH400 provides sufficient power when operating with +12/+24VDC auxiliary power supplies.
Directly connect the door peripherals identified in "Step 1 - Identify System Components" on page 2 to the I/O ports
of the EDGE EVO Hi-O Edge Door Module (EDM-M). Consult the EDM-M datasheet to determine the available current
capacity for the selected input power scheme of the EH400.
Ensure all door peripherals connected to the Strike/AUX relays and the Reader DC PWR Output or both do not exceed
1.2 Amps (AUX Input) or 400mA (PoE Input) combined. Alternatively, connect the door peripherals to the Strike/AUX
relays configured for Dry contact up to 2 Amps per relay.
4
INSTALLATION GUIDE
+ I
+ I
+ I
+ I
dps
mag
rex
alarm
Hi-O iCLASS reader
- EVM), adding approximately 5 to 10mA for overall load requirements.
Port
CAN DC PWR
Output (MAX)
+ ... + I
EDM-M
) to the output current capacity of the EH400 (see "Specifications" on page
total
Conditions
AUX +12/24 VDC Input
PoE Input
V out
+10.8 to
+24VDC
+24VDC (NOM)
©2009 - 2012 HID Global Corporation. All rights reserved.
82000-920, D.1
I out
1.2Amp
400mA