AutomationDirect Stride SIO-MB04RTDS Podręcznik użytkownika - Strona 4
Przeglądaj online lub pobierz pdf Podręcznik użytkownika dla Systemy wejścia/wyjścia AutomationDirect Stride SIO-MB04RTDS. AutomationDirect Stride SIO-MB04RTDS 12 stron. Temperature input module: rtd, 4-channel
Również dla AutomationDirect Stride SIO-MB04RTDS: Skrócona instrukcja obsługi (2 strony)
DESCRIPTION OF MODBUS REGISTERS
40002 / 40003: FIRMWARE
Two read-only registers, containing the firmware version.
40007: NODE ID
Contains the Modbus address of the device; the values allowed are from 1 to 245 decimal.
This value must match the Modbus address of the connected Modbus device (data source).
Default value: 1 Decimal (01 Hex). INIT value: 245 Decimal (F5 Hex).
40011: SYSTEM FLAGS
Contains the enable bits and system event identifiers. The following parameters are configurable:
Watchdog Event Enable: this bit enables the Watchdog Event (0=Watchdog Disabled, 1 =Watchdog Enabled). If the Watchdog
is enabled and the Watchdog Timer (configured in register 40013) expires before this device receives a Modbus command, the
green PWR LED blinks and the Watchdog Event bit is set to 1. This bit must be set in logic on power up.
Watchdog Event: this bit is set to 1 when the Watchdog Timer expires before this device receives a Modbus command. This bit must
be reset manually after a Watchdog event.
Power Up Event: this bit is forced to 1 at each time power is applied to the device to indicate that the device has been switched off
or reset. With the setting of this bit as 0 (by the user) and checking its state, it is possible to know if a reset of the device has occurred
(0 = reset not occurred; 1 = reset occurred). This bit must be reset manually.
Bit
15
14
Coil
-
-
Description
40013: WATCHDOG TIMER
Contains the value of the Watchdog timer, in seconds. If the Watchdog is enabled and the device doesn't receive a command before
this timer expires, the Watchdog bit will be set to 1 (see the description of "System Flags"). Default value: 10 (10 sec.).
40031: INPUT TYPE CHANNEL 0
This register shows the type of sensor configured for this input (see "Input Type Table").
Default: Pt100 (0D Hex)
Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Description
40032: INPUT TYPE CHANNEL 1
This register shows the type of sensor configured for this input (see "Input Type Table").
Default: Pt100 (0D Hex)
Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Description
SIO-MB04RTDS User Guide, 1st Edition
13
12
11
10
09
08
-
-
-
163 162 161
07
06
05
04
03
02
-
-
-
-
-
-
Watchdog Event enable
Watchdog Event
Power Up Event
Input Type #0
Input Type #1
Stride Field I/O
01
00
-
-
INPUT TYPE TABLE
Type
Value (Hex)
Disabled
Resistor 0–2000 Ohm
Resistor 0–500 Ohm
Pt100
Ni100
Pt1000
Ni1000
Pot. < 50 kOhm
00h
12h
0Ch
0Dh
0Fh
0Eh
10h
11h
3