Voltage Input
1. Access the Initial Setup mode by pressing and holding the
inpt
, use the
,
and
.
buttons to select the value that corresponds to the voltage input that will be
applied to the controller. See the table for voltage specifications. Press the
value. The controller will display the module information splash screen for three seconds and then return to
the main screen.
2. Press the
;
button for three seconds again. Press the
Use the
,
and
.
buttons to select the high engineering value that corresponds to the maximum voltage
signal that will be applied to the input of the controller. For example, if the
is the value the controller will display when the input equals 5V. Press the
value. Press the
'
button to access the parameter
low engineering value that corresponds to the minimum voltage signal that will be applied to the input of the
controller. For example, if the
V5
0V-5V input is to be used, this is the value the controller will display when the
input equals 0V. Press the
;
button twice to save the selected value and return to the controller main screen.
3. Press the
'
button repeatedly until the parameter
0
,
1
,
2
or
3
to indicate the position of the decimal point for the PV and SV values on the controller. Press the
;
button twice to save the selected value and return to the controller main screen.
4. If the voltage input PV value displayed on the controller needs to be adjusted, press the
than 3 seconds. Press the
'
button repeatedly until the parameter
buttons to adjust a positive or negative offset to the PV value displayed on the controller. Press the
twice to save the selected value and return to the controller main screen.
Voltage Input Type and Input Range
Voltage Input Type
0~50mV Analog Input
0V~10V Analog Input
0V~5V Analog Input
11-3
Current Input
1. Install the supplied 249 ohm resistor between terminal #4 and #6.
2. Access the Initial Setup mode by pressing and holding the
inpt
, use the
,
and
.
buttons to select the value that corresponds to the current input that will be
applied to the controller. See the table for current specifications. Press the
value. The controller will display the module information splash screen for three seconds and then return to the
main screen.
3. Press the
;
button for three seconds again. Press the
appears. Use the
,
and
.
buttons to select the high engineering value that corresponds to the maximum
current signal that will be applied to the input of the controller. For example, if the
used, this is the value the controller will display when the input equals 20mA. Press the
the selected value. Press the
'
button to access the parameter
to select the low engineering value that corresponds to the minimum current signal that will be applied to the
input of the controller. For example, if the
ma4
display when the input equals 4mA. Press the
controller main screen.
4. Press the
'
button repeatedly until the parameter
0
,
1
,
2
or
3
to indicate the position of the decimal point for the PV and SV values on the controller. Press the
;
button twice to save the selected value and return to the controller main screen.
5. If the current input PV value displayed on the controller needs to be adjusted, press the
than 3 seconds. Press the
'
button repeatedly until the parameter
buttons to adjust a positive or negative offset to the PV value displayed on the controller. Press the
twice to save the selected value and return to the controller main screen.
Current Input Type and Range
Current Input Type
4~20mA Analog Input
0~20mA Analog Input
12-1
PID Control Setup
Note: Select the desired control mode before beginning PID Control Setup.
There are four groups for storing PID parameters,
less than three seconds and press the
'
,
and
.
buttons to select which group to use for storing the PID parameters. Press the
confirm the setting. The groups
pid0
-
pid3
in the control process. If the group
pid4
is selected, the controller will automatically select the most useful
PID parameters based on the current temperature setting and the SV value set in each PID group.
The parameters for PID can be auto-tuned using the
;
button for less than three seconds. Use the
button to save the value. Optimal PID values are automatically determined with the auto-tune feature. PID
operation can also be controlled by programming the individual
Access these parameters by pressing the
;
repeatedly until the parameter
pn
appears where
the
,
and
.
buttons to change the value for the Proportional band if desired and press the
save the value. Press the
'
button to access the
the value for the Integral time if desired and press the
access the
dn
parameter. Use the
,
and
and press the
;
button twice to save the value and return to the controller main screen.
12-2
Heating Loop with PID Control
1. Access the Initial Setup mode by pressing and holding the
button repeatedly until the parameter
Ctrl
control. Press the
'
button to access the parameter
ed for controlling a heating loop. Press the
;
2. Press the
'
button to access the parameter
the
;
button to return to the controller main screen.
3. Refer to Section 12-1 of this Quick Start Guide to set up the PID control parameters.
4. If the temperature controller's output #1 is discrete, access the regulation mode again by pressing the
button for less than three seconds. Press the
'
the
,
and
.
buttons to set the time period in seconds for the heating control. Press the
to save the value and return to the controller main screen.
;
button for three seconds. In the parameter
;
button to save the selected
'
button to access the parameter
V5
0V-5V input is to be used, this
;
button to save the selected
tp-l
. Use the
,
and
.
buttons to select the
sp
appears. Use the
,
and
.
;
tpof
appears. Use the
LED Display
Engineering Range
-999 ~ 9999
mv
-999 ~ 9999
v10
-999 ~ 9999
v5
;
button for three seconds. In the parameter
;
button to save the selected
'
button repeatedly until the parameter
ma4
4-20mA input is to be
;
tp-l
. Use the
,
4-20mA input is to be used, this is the value the controller will
;
button twice to save the selected value and return to the
sp
appears. Use the
,
and
.
;
tpof
appears. Use the
LED Display
Engineering Range
-999 ~ 9999
ma4
-999 ~ 9999
ma0
pid0
(PID0) -
pid3
(PID3). Press the
button repeatedly until the parameter
pid0
can be individually set up with different SV values to be used
At
parameter. Access this parameter by pressing the
.
button to turn the auto-tune feature
on
p
,
i
, and
d
parameters for each PID group.
button for less than three seconds and press the
n
corresponds to the PID group you are programming. Use
in
parameter. Use the
,
and
.
;
button to save the value. Press the
.
buttons to change the value for the Derivative time if desired
;
button for three seconds. Press the
appears. Confirm the default value
Pid
is selected for PID
s-hC
.
Confirm the default value
button to return to the controller main screen.
r-s
. Verify that the default value
run
button repeatedly until the parameter
htpd
12-3
Heating Loop with ON / OFF Control
1. Access the Initial Setup mode by pressing and holding the
button until the parameter
control. Press the
;
Confirm the default value
the control
ler main screen.
2. Press the
'
button to access the parameter
tp-h
.
the
;
button to return to the controller main screen.
3. Press the
;
button for less than three seconds to access the parameter
buttons to enter hysteresis. This is the amount the PV must go below the SV before the controller output turns
on. Press the
;
button twice to save the selected value and return to the controller main screen.
12-4
Cooling Loop with PID Control
buttons to select
1. Access the Initial Setup mode by pressing and holding the
button repeatedly until the parameter
control. Press the
button for less
controlling a cooling loop. Press the
,
and
.
2. Press the
'
button to access the parameter
;
button
the
;
button to return to the controller main screen.
3. Refer to Section 12-1 of this Quick Start Guide to set up the PID control parameters.
4. If the temperature controller's output #1 is discrete, access the regulation mode again by pressing the
button for less than three seconds. Press the
the
,
and
.
buttons to set the time period in seconds for the cooling control. Press the
to save the value and return to the controller main screen.
12-5
Cooling Loop with ON / OFF Control
1. Access the Initial Setup mode by pressing and holding the
button repeatedly until the parameter
/ OFF control. Press the
Use the
.
button to select
value and return to the controller main screen.
2. Press the
'
button to access the parameter
the
;
button to return to the controller main screen.
3. Press the
;
button for less than three seconds to access the parameter
buttons to enter hysteresis. This is the amount the PV must go above the SV before the controller output turns
on. Press the
;
button twice to save the selected value and return to the controller main screen.
tp-h
12-6
Dual Heating / Cooling Loop with PID Control
button to save
and
.
buttons
1. Access the Initial Setup mode by pressing and holding the
button repeatedly until the parameter
control. Press the
controlling a dual heating / cooling loop. This parameter sets the heating control to output #1 and the cooling
control to output #2. Press the
buttons to select
2. Press the
'
button to access the parameter
the
;
button to return to the controller main screen.
3. Refer to Section 12-1 of this Quick Start Guide to set up the PID control parameters.
button for less
4. If the temperature controller's output #1 is discrete, access the regulation mode again by pressing the
,
and
.
button for less than three seconds. Press the
;
button
the
,
and
.
buttons to set the time period in seconds for output #1, the heating control. Press the
button to save the value. If the temperature controller's output #2 is discrete, press the
until the parameter
output #2, the cooling output. Press the
screen.
5. Optional regulation parameters can be programmed for a second
control output. If this is desired, access the regulation mode again by
pressing the
;
button until the parameter
control to have a different proportional setting than the heating loop. The
heating loop proportional band setting is multiplied by the
to create a proportional band setting for the cooling loop control. Use the
,
and
.
buttons to change this value if desired. Press the
button to save the selected value. Press the
;
button for
parameter
dead
. Use the
appears. Use the
zone value around the setpoint where the output is not effected by the
;
button to
proportional control value. As long as the PV remains within the deadband
zone the output is not affected by the proportional control. The integral
and derivative controls ignore the deadband setting and may cause the
output to be on within the deadband zone. Press the
save the value and return to the controller main screen.
. Press the
;
12-7
Dual Heating / Cooling Loop with ON / OFF Control
1. Access the Initial Setup mode by pressing and holding the
'
button
button repeatedly until the parameter
ON / OFF control and press the
;
button to
parameter
s-hC
. Use the
buttons to change
sets the heating control to output #1 and the cooling control to output #2. Press the
'
button to
the value and return to the controller main screen.
2. Press the
'
button to access the parameter
the
;
button to return to the controller main screen.
3. Press the
;
button for less than three seconds to access the
parameter
hts
. Use the
for output #1, the heating control. This is the amount the PV must go
below the SV before the controller output turns on. Press the
'
button to save the selected value. Press the
the parameter
Cts
heat
is select-
esis for output #2, the cooling control. This is the amount the PV
must go above the SV before the controller output turns on. Press
is selected. Press
the
;
button twice to save the selected value and return to the
controller main screen.
4. Optional regulation parameters can be programmed for additional dual loop control. If this is desired, access
the regulation mode again by pressing the
;
appears. Use
repeatedly until the parameter
value around the setpoint where the output is not on. The PV must go beyond the deadband range in order for
;
button twice
either the heating or cooling output to turn on. Press the
to the controller main screen.
;
Ctrl
appears. Use the
,
and
.
button to save the value. Press the
'
heat
is selected for controlling a heating loop. Press the
r-s
. Verify that the default value
;
Ctrl
appears. Confirm the default value
'
button to access the parameter
s-hC
;
button twice to save the value and return to the controller main screen.
r-s
. Verify that the default value
'
button repeatedly until the parameter
;
Ctrl
appears. Use the
,
;
button to save the value. Press the
'
Cool
for controlling a cooling loop. Press the
r-s
. Verify that the default value
;
Ctrl
appears. Confirm the default value
'
button to access the parameter
s-hC
;
button twice to save the value and return to the controller main screen.
r-s
. Verify that the default value
'
button repeatedly until the parameter
hCpd
appears. Use the
,
and
.
buttons to enter the cycle period in seconds for
;
button twice to save the value and return to the controller main
button for less than three seconds. Press the
Coef
appears. This value allows the cooling
Coef
'
button to access the
,
and
.
buttons to enter a deadband
;
button twice to
;
Ctrl
appears. Use the
;
button to save the selected value. Press the
.
button to select
h1C2
for controlling a cooling / heating loop. This parameter
r-s
. Verify that the default value
,
and
.
buttons to enter hysteresis
;
'
button to access
. Use the
,
and
.
buttons to enter hyster-
;
button for less than three seconds. Press the
dead
appears. Use the
,
and
;
button twice to save the selected value and return
button for three seconds. Press the
'
buttons to select
onof
for ON / OFF
button to access the parameter
s-hC
.
button to return to
;
run
is selected. Press
hts
. Use the
,
and
.
button for three seconds. Press the
'
Pid
is selected for PID
. Use the
.
button to select
Cool
for
run
is selected. Press
;
Clpd
appears. Use
;
button twice
button for three seconds. Press the
'
and
.
buttons to select
onof
for ON
button to access the parameter
s-hC
.
;
button twice to save the
run
is selected. Press
Cts
. Use the
,
and
.
button for three seconds. Press the
'
Pid
is selected for PID
. Use the
.
button to select
h1C2
for
run
is selected. Press
;
htpd
appears. Use
;
'
button repeatedly
dead
Dead band: dead
Output
band width=positive
'
Heating
Cooling
PV
0
Set point
value
Dual control with PID
positive deadband
;
dead
Dead band: dead
Output
band width=negative
Heating
Cooling
PV
0
Set point
Dual control with PID
negative deadband
button for three seconds. Press the
'
,
and
.
buttons to select
onof
for
'
button to access the
;
button twice to save
run
is selected. Press
dead
Dead band
hts
Cts
Heating hysteresis
Cooling hysteresis
ON
Heating
Cooling
OFF
PV
Set point
Dual loop ON / OFF control
output operation
'
button
.
buttons to enter a deadband zone