Item
Parameter Name
16
Keypad Scroll Delay
18
Power-Up Mode
19
Power-Up Value
20
Display Value at Minimum Output
21
Display Value at Maximum Output
Output % - Minimum
25
(in 1/10 percent units)
Output % - Maximum
26
(in 1/10 percent units)
IronHorse GSDA-DP-S User Manual – 1st Edition – 09/18/2019
This parameter sets the scroll speed for the front-panel push
buttons� The function of this parameter varies slightly depending
on the Keypad Mode� See parameter 15 for more details�
This parameter defines the mode which determines the default
Running Value when power is initially applied to the GSDA-DP-S�
• Mode 1: Default to Zero
When in this mode, the unit will default to zero (display units)�
• Mode 2: Default to Power-Up Value
When in this mode, the unit will default to the Power-up Value,
parameter 19�
• Mode 3: Default to Previously Running Value
When in this mode, the unit will default to the previous running
value before power was removed� A previous running value
must have been active for at least 3 seconds to be recalled after
power has been disconnected and reapplied�
When Power-up Mode is set to 2, this parameter will designate the
default display value at power-up in display units�
Display and Output Setup
This parameter defines the lower end of the display range� This
is the value which limits how low the user is able to scroll the
displayed value in Running Mode� This parameter is set without
consideration for the decimal point's position� For example,
setting this parameter to 125 would set the lower display limit
at 12�5, 0�125, or 125 according to the other configuration
parameters�
This parameter defines the upper end of the display range� This
is the value which limits how high the user is able to scroll the
displayed value in Running Mode� This parameter is set without
consideration for the decimal point's position� For example,
setting this parameter to 1000 would set the upper display limit
at 100�0, 1�000, or 1000 according to the other configuration
parameters�
This parameter sets the output percentage which corresponds to
the minimum display value, parameter 20� This parameter has
a range of 0 to 1000 which represents 0�0 to +100�0 percent of
output� When the user is adjusting the display value towards the
programmed minimum display, the output will linearly approach
the value of this parameter� For example, setting this parameter
to 25 will configure the GSDA-DP-S to output 2�5% when the user
adjusts the display value to equal the display minimum, parameter
20� See parameters 20 - 22 and the application examples for
additional information�
This parameter sets the output percentage which corresponds to
the maximum display value, parameter 21� This parameter has
a range of 0 to 1000 which represents 0�0 to +100�0 percent of
output� When the user is adjusting the display value towards the
programmed maximum display, the output will linearly approach
the value of this parameter� For example, setting this parameter to
850 will configure the GSDA-DP-S to output 85�0% when the user
adjusts the display value to equal the display maximum, parameter
21� See parameters 20 - 21and the application examples for
additional information�
Description
Page 13