Automationdirect.com Productivity 2000 P2-04DA Podręcznik - Strona 3
Przeglądaj online lub pobierz pdf Podręcznik dla Jednostka sterująca Automationdirect.com Productivity 2000 P2-04DA. Automationdirect.com Productivity 2000 P2-04DA 8 stron. Analog output
Wiring Diagram
Voltage Output
V+
0 - 10
VDC Load
COM
AC or DC
V+
±10 VDC
Load
COM
AC or DC
NOTE: Shield is connected to
common at the source device.
Sales 800-633-0405
Current Source Output
(Field device is sinking)
I+
4 - 20mA
COM
Load
I-
24 VDC User
-
+
Supplied Power
I+
4-wire
COM
4 - 20mA Load
I-
AC or DC
-
+
Transmitter
Power Supply
24 VDC User
Supplied Power
Current Sink Output
(Field device is sourcing)
+24VDC User
Supplied Power
2-wire
I-
4 - 20mA Load
COM
Install
Jumper
I+
24VDC+
4-wire
I-
4 - 20mA Load
COM
Install
AC or DC
Jumper
I+
Transmitter
Power Supply
Schematic
24VDC+
V1+
I1-
I1+
COM
V2+
I2-
I2+
24VDC+
24 VDC User
24VDC-
-
+
Supplied Power
V3+
I3-
I3+
COM
V4+
I4-
I4+
24VDC+
www.productivity2000.com
INTERNAL
MODULE CIRCUITRY
voltage sink/source
4-20 mA current sinking
4-20 mA current sourcing
voltage sink/source
4-20 mA current sinking
4-20 mA current sourcing
voltage sink/source
4-20 mA current sinking
4-20 mA current sourcing
voltage sink/source
4-20 mA current sinking
4-20 mA current sourcing
ANALOG
CIRCUIT
POWER
ANALOG
CIRCUIT COMMON
CH1
DAC
CH2
DAC
CH3
DAC
CH4
DAC
3