Aire 3828AR7314S Instrukcja instalacji - Strona 15

Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Klimatyzator Aire 3828AR7314S. Aire 3828AR7314S 16 stron. Single split wall mounted air conditioner

Soap water method
(1) Remove the caps from the 2-way and 3-way
valves.
(2) Remove the service-port cap from the 3-way
valve.
(3) To open the 2-way valve turn the valve stem
counterclockwise approximately 90°, wait for
about 2~3 sec, and close it.
(4) Apply a soap water or a liquid neutral detergent
on the indoor unit connection or outdoor unit
connections by a soft brush to check for
leakage of the connecting points of the piping.
(5) If bubbles come out, the pipes have leakage.
Evacuation
C
Connect the charge hose end described in the
preceding steps to the vacuum pump to
evacuate the tubing and indoor unit.
Confirm the "Lo" knob of the manifold valve is
open. Then, run the vacuum pump.
The operation time for evacuation varies with
tubing length and capacity of the pump. The
following table shows the time required for
evacuation.
Required time for evacuation when 30 gal/h
vacuum pump is used
If tubing length is less
if tubing length is longer
than 10m (33 ft)
10 min. or more
When the desired vacuum is reached, close the
"Lo" knob of the manifold valve and stop the
vacuum pump.
Finishing the job
D
With a service valve wrench, turn the valve stem
of liquid side valve counter-clockwise to fully
open the valve.
Turn the valve stem of gas side valve
counter-clockwise to fully open the valve.
Loosen the charge hose connected to the gas side
service port slightly to release the pressure, then
remove the hose.
Replace the flare nut and its bonnet on the gas side
service port and fasten the flare nut securely with an
adjustable wrench. This process is very important to
prevent leakage from the system.
Replace the valve caps at both gas and liquid side
service valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready to test run.
than 10m (33 ft)
15 min. or more
15
3-way valve
(Close)
2-way valve
(Open)
Hexagonal wrench
Indoor unit
Outdoor unit
Manifold valve
Pressure
Lo
Hi
gauge
Open
Vacuum pump
Gas side
Liquid side
Cap
Close