LINE SET

INSTALLATION

Line Set Isolation - The following illustrations are
examples of proper refrigerant line set isolation:
REFRIGERANT LINE SET — TRANSITION
FROM VERTICAL TO HORIZONTAL
ANCHORED HEAVY NYLON
WIRE TIE OR AUTOMOTIVE
MUFFLER‐TYPE HANGER
WALL
STUD
NON-CORROSIVE
METAL SLEEVE
REFRIGERANT LINE SET — INSTALLING
HORIZONTAL RUNS
To hang line set from joist or rafter, use either metal strapping material
or anchored heavy nylon wire ties.
8 FEET (2.43 METERS)
STRAPPING
MATERIAL (AROUND
SUCTION LINE
FLOOR JOIST OR
ONLY)
ROOF RAFTER
TAPE OR
WIRE TIE
FLOOR JOIST OR
ROOF RAFTER
AUTOMOTIVE
MUFFLER‐TYPE HANGER
STRAP LIQUID LINE TO
SUCTION LINE
LIQUID LINE
SUCTION LINE -
WRAPPED IN ARMAFLEX
WIRE TIE (AROUND
SUCTION LINE
ONLY)
8 FEET (2.43 METERS)
NON-CORROSIVE
METAL SLEEVE
STRAP THE SUCTION LINE TO THE
JOIST OR RAFTER AT 8 FEET (2.43
METERS) INTERVALS THEN STRAP
THE LIQUID LINE TO THE SUCTION
LINE.
IMPORTANT — Refrigerant lines must not contact structure.
REFRIGERANT LINE SET — INSTALLING
VERTICAL RUNS (NEW CONSTRUCTION SHOWN)
NOTE - Insulate liquid line when it is routed through areas where the
surrounding ambient temperature could become higher than the
temperature of the liquid line or when pressure drop is equal to or
greater than 20 psig.
IMPORTANT - Refrigerant lines must not contact wall
OUTSIDE WALL
WOOD BLOCK
BETWEEN STUDS
TAPE OR
WIRE TIE
NOTE - Similar installation practices should be used if line set is
to be installed on exterior of outside wall.
FIGURE 5
Page 4