Parameter Group

SV setting
※ Parameter setting order
Parameter group 2
The parameters are related to each other. Please set the parameters in the order above.
※ When there is no key input for 60 sec while in SV setting mode or parameter groups, the unit will return to RUN mode
automatically.
● Parameter group 1
3 sec
RUN mode
3 sec
PV display
SV 2
SU-2
temperature
※ 2
Event 1
alarm
AL1
temperature
Event 2
alarm
AL2
temperature
LBA
monitoring
LBA
time
Alarm
output
AHYS
hysteresis
Proportional
P
band
Integral
I
time
Derivative
D
time
Control
T
period
Hysteresis
HYS
Input
IN-B
correction
Manual
REST
reset
Ramp
RAPU
up time
Ramp
RAPD
down time
Lock
LOC
RUN mode
3 sec
Parameter group 1
3 sec
Parameter group 1
※ 1:
:
( )key-Switch fields,
※ 2: Press the
save the setting value and move to the next parameter.
※ Hold the
key for 3 sec anytime during parameter settings to save the setting
value and return to RUN mode.
※ The dotted line parameters
parameter settings.
SV display
※ 1
Setting range: refer to '
0
Setting range: refer to '
10
※ [AL1, AL2] parameters do not appear when Event 1/2 [EU-1, EU-2] of parameter
group 2 is set to AL-0, LBA, SBA.
※ [AL2] parameter only appears in models that support Event 2 output.
10
Setting range: 0 to 999 sec
※ Only appears when Event1/2 [EU-1, EU-2] of parameter group 2 is set to LBA.
600
※ Does not appear in current output models.
Setting range: 1 to 100℃/℉ (0.1 to 100.0℃/℉)
2
※ Does not appear when Event 1/2 [EU-1, EU-2] of parameter
group 2 is set to AL-0, LBA, SBA.
Setting range: 0.0 to 100.0%
#0
※ ON/OFF control: Set to )0, PID control: Set to over )0
Setting range: 0 to 3,600 sec
0
※ Integral operation is turned OFF when set to 0.
Setting range: 0 to 3,600 sec
0
※ Derivative operation is turned OFF when set to 0.
Setting range: 1 to 120 sec
20
※ Set to a small value in SSR drive output models. (e.g. 2 sec)
※ Does not appear in current output models.
Setting range: 1 to 100℃/℉ (0.1 to 100.0℃/℉)
2
※ Only appears during ON/OFF control (proportional band [P] set to )0).
0
Setting range: -49 to 50℃/℉ (-50.0 to 50.0℃/℉)
Setting range: 0.0 to 100%
※ Only appears when P control (proportional band [P] set to over )0, integral time [I],
)0
and derivative time [D] are set to 0)
10
Setting range: 1 to 99 min
※ Only appears when ramp function [RAMP] of parameter group
2 is set to ON.
10
OFF
ON
Dual PID Control
Parameter group 2
SV setting
,
key-Change values
key after checking or changing the values in parameter settings to
may not appear depending on the model or other
Input Type and Range'.
Input Type and Range'.
Setting range:
Unlock
OFF
Lock parameter 1 (
ON
ON1
Lock parameter 1 (
ON1
SENSORS
+
3 sec
CONTROLLERS
3 sec
MOTION DEVICES
SOFTWARE
(J)
Temperature
Controllers
(K)
SSRs
(L)
Power
Controllers
(M)
Counters
(N)
Timers
(O)
Digital
Panel Meters
(P)
Indicators
(Q)
Converters
※ Only appears during PID
(R)
control (proportional band
Digital
Display Units
[P] set to over )0).
(S)
Sensor
Controllers
(T)
Switching
Mode Power
Supplies
(U)
Recorders
(V)
HMIs
(W)
Panel PC
(X)
Field Network
Devices
key available)
key unavailable)
J-149