Autonics FXY Series Instrukcja obsługi produktu - Strona 3

Przeglądaj online lub pobierz pdf Instrukcja obsługi produktu dla Przyrządy pomiarowe Autonics FXY Series. Autonics FXY Series 4 stron. Digital counters/ timers (indicator
Również dla Autonics FXY Series: Podręcznik (6 strony), Instrukcja obsługi (6 strony)

Autonics FXY Series Instrukcja obsługi produktu
Detach the Case
Lever
DIP Switch Setting
1
2 3 4 5 6 7 8 9 10
OFF
ON
SW
Function
SW
Counter
Timer
-
1
Time range
2
Input operation mode
3
Count up / count down
4
5
Max. counting speed
-
6
Front [RESET] key
7
Memory retention
8
9
Counter / Timer
CP1, CP2, INHIBIT, RESET input logic
10
• [Counter] Input operation mode
SW
Count up / count down &
input operation mode
2
3
4
Up / Down - A
OFF OFF OFF
(command)
Up / Down - B
ON
OFF OFF
Count
(individual)
up
Up / Down - C
OFF ON
OFF
(phase difference)
UP
ON
ON
OFF
Up / Down - D
OFF OFF ON
(command)
Up / Down - E
ON
OFF ON
Count
(individual)
down
Up / Down - F
OFF ON
ON
(phase difference)
Down
ON
ON
ON
• [Counter] Max. counting speed
SW
Max. counting speed
5
6
1 cps
ON
OFF
OFF
OFF
30 cps
2 kcps
OFF
ON
5 kcps
ON
ON
• Front [RESET] key
SW-7
Front [RESET] key
Use
ON
Not used
OFF
• Counter / Timer
SW-9
Counter / Timer
Counter
ON
Timer
OFF
• Press the both levers and pull them from the
front to detach the case and the terminal. DIP
switch is located inside.
᜸ Caution: Turn OFF the power before
detaching the case.
• Detach the case and proceed the
settings. See the 'Detach the Case.'
• How to change the settings:
power OFF → change settings → power
ON → press [RESET] key or input the
RESET signal (≥ 20 ms) to the external
terminal.
Defaults
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
• [Timer] Time range
SW
Time range
1
2
3
4-digit
6-digit
OFF OFF OFF 99.99 s
99999.9 s
ON
OFF OFF 999.9 s
999999 s
OFF 9999 s
99 m 59.99 s
OFF ON
OFF 99 m 59 s
999 m 59.9 s
ON
ON
OFF OFF ON
999.9 m
99999.9 m
99 h 59 m 99 h 59 m 59 s
ON
OFF ON
999.9 h
9999 h 59 m
OFF ON
ON
ON
ON
ON
9999 h
99999.9 h
• Memory retention
SW-8
Memory retention
×
ON
OFF
• Input logic
SW-10
Input logic
NPN (no-voltage input)
ON
PNP (voltage input)
OFF
Input Connections
• Input: CP1, CP2 (INHIBIT), RESET
• Max. counting speed in the contact input: 1 or 30 cps setting (counter).
■ No-voltage (NPN) input
• Solid-state input
Sensor
(NPN output)
Counter / Timer
Brown
+12 V
5.4 kΩ
Black
Internal circuit
of input part
Blue
0 V
• Contact input
Counter / Timer
+12 V
5.4 kΩ
Internal circuit
of input part
0 V
■ Voltage (PNP) input
• Solid-state input
Sensor
(PNP output)
Counter / Timer
Brown
+12 V
Black
Internal circuit
of input part
10.8 kΩ
Blue
0 V
• Contact input
Counter / Timer
+12 V
Internal circuit
of input part
10.8 kΩ
0 V
Sensor
(NPN open collector output)
Counter / Timer
Brown
+12 V
5.4 kΩ
Black
Internal circuit
of input part
Blue
0 V
Sensor
(PNP open collector output)
Counter / Timer
Brown
+12 V
Black
Internal circuit
of input part
10.8 kΩ
Blue
0 V