Mode Setting
→
Parameter group
[M] for over 3 sec
→
[M]
[▼]+[▲] for over 1
RUN
→
sec after remove the
external pressure
Max / Min monitoring
→
[▲] for over 3 sec
01) Max. / Min. pressure value is available to check by monitoring.
[Option external input model] Auto shift judgment level checking / setting is available when P-9 External input
terminal is set as SHFT. (no input displays 0)
Parameter Setting
• Some parameter are activated / deactivated depending on other parameters. Refer to
the description.
• The setting item name and setting value are cross-displayed on the display part.
• It returns to RUN mode when there is no additional key input for 60 sec in each
parameter group.
• Guaranteed write life: 100,000 times
• [M] key: Saves setting value and moves to next parameter
] key: Selects setting value
[▼], [▲
Parameter
Display Default Setting range
KPA
P-1
Display unit
UNIT
MPA
OUT
P-2
operation
OUtM
OFF
mode
P-3
Output type
NoNC
1O2O
Response
P-4
@5 2.5, 5.0, 100, 500, 1,000 ms
time
SPD
Voltage low
P-5
limit scale
A-1V
)0
Voltage high
P-6
limit scale
A-5V
10)0
Current low
P-7
limit scale
A-04
)0
Current high
P-8
limit scale
A-20
10)0
External
P-9
input
D-IN
HOLD
terminal
Auto shift
P-10
output
01)
ShOT
OUT1
P-11 Lock
LOCK
LOC1
01) Condition: P-9. External input terminal SHFT setting
[M] for over 3 sec
Preset setting
[M]
Zero-point
Displays 0.0 and
returns automatically
adjustment
[M]
Reset or set: [▼]+[▲]
/ Auto shift
01)
for over 1 sec
[Negative / Compound pressure model]
kPa, KGC: kgf/cm
, bar, psi, mmHg, inHg, H2O: mmH
2
[Static pressure model]
MPa, kPa, KGC: kgf/cm
, bar, psi
2
HYS.M: Hysteresis
WIN: Window comparison output
HY-W: Hysteresis-Window comparison output
AUTO: Auto sensitivity setting
F.OUT: Forced output control
OUT1
OUT2
1O2O Normally open
Normally open
1O2C Normally closed Normally open
1C2O Normally closed Normally open
1C2C Normally closed Normally closed
[Option voltage output model]
Min. rated pressure ≤ Low limit scale ≤ 90% of rated
pressure
[Option voltage output model]
Low limit scale setting value + 10% of rated pressure ≤
High limit scale ≤ Max. rated pressure
[Option current output model]
Min. rated pressure ≤ Low limit scale ≤ 90% of rated
pressure
[Option current output model]
Low limit scale setting value +10% of rated pressure ≤
High limit scale ≤ Max. rated pressure
[Option external input model]
HOLD: Hold
SHFT: Auto shift
[Option external input model]
OUT1, OUT2, ALL
LOC1: Parameter, preset, zero-point adjustment setting
lock / Monitoring value reset lock
LOC2: Parameter lock (available to check setting value)
OFF
Preset setting
■ Setting method
→
• Setting name and value are cross-displayed in SV display part.
→
1. Set the operation mode in P-2 OUT operation mode.
2. Enter the preset setting mode by pressing [M] key from RUN mode.
RUN
→
3. Select the setting item by [M] key and change the preset by [▼] or [▲] key.
4. Press [M] key to save setting or no key input over 60 sec not to save setting and
→
return to RUN mode. (except forced output control mode)
→
■ Preset setting by operation mode
Operation mode
Hysteresis
HYsM
Window
comparison
output
WIN
01)
O
2
Hysteresis-
Window
comparison
HY-W
output
02)
Auto
sensitivity
setting
AUTO
Forced output
fOUT -
control
04)
01) Hysteresis: 1 (min display interval, fixed)
02) ST1 = HYS1, actual hysteresis is 1 (min. display interval)
03) When error appears, check setting conditions and set protper setting values.
04) [Option external input model] Forced output does not support external input terminal.
■ Precaution
• The preset value (default) of the changed operation mode is set when changing P-2
OUT operation mode setting.
• Preset value is converted as the changed unit automatically when changing P-1
Display unit setting.
• Preset is reset when changing P-9 External input terminal setting.
■ Default setting value
Operation mode
Hysteresis
HYsM
Window
comparison
output
WIN
Hysteresis-
Window
comparison
HY-W
output
Auto
sensitivity
setting
AUTO
Forced output
fOUT -
control
Preset
Setting range
Pressure
Min. display pressure < ST1 ≤ Max. display
detection level 1
pressure
ST1
Hysteresis level 1 HYS1 Min. display pressure ≤ HYS1 < ST1
Pressure
Min. display pressure < ST2 ≤ Max. display
detection level 2
pressure
ST2
Hysteresis level 2 HYS2 Min. display pressure ≤ HYS2 < ST2
Pressure
Min. display pressure ≤ LO-1 ≤ Max.
detection low
display pressure -(3 × Min display interval)
limit 1
LO-1
Pressure
LO-1 + (3 × Min display interval) ≤ HI-1 ≤
detection high
Max. display pressure
limit 1
HI-1
Pressure
Min. display pressure ≤ LO-2 ≤ Max.
detection low
display pressure - (3 × Min display interval)
limit 2
LO-2
Pressure
LO-2 + (3 × Min display interval) ≤ HI-2 ≤
detection high
Max. display pressure
limit 2
HI-2
Pressure
Min. display pressure < ST1 ≤ Max. display
detection level 1
pressure
ST1
Hysteresis level 1 HYS1 Min. display pressure ≤ HYS1 < ST1
Pressure
Min. display pressure ≤ LOW ≤ Max.
detection low
display pressure - (3 × Min display interval)
limit
LOW
Pressure
Low + (3 × Min display interval) ≤ HIGH ≤
detection high
Max. display pressure
limit
HIGH
Min. display pressure ≤ ST1 ≤ Max. display
Pressure level 1
pressure - 1% of rated pressure
ST1
ST1 + 1% of rated pressure ≤ ST2 ≤ Max.
Pressure level 2
03)
display pressure
ST2
Auto setting
Pressure
• Manual setting is possible by [▼] or [▲]
detection level
SET
key.
• Manual ON/OFF for OUT1/2 is possible by
-
[▼] or [▲] key.
Negative
Static
Preset
0.1 kPa
0.1 kPa
ST1 -50.0
50.0
HYS1 0.0
0.0
ST2 -50.0
50.0
HYS2 0.0
0.0
LO-1 0.0
0.0
HI-1 -50.0
50.0
LO-2 0.0
0.0
HI-2 -50.0
50.0
ST1 -50.0
50.0
HYS1 0.0
0.0
LOW 0.0
0.0
HIGH -50.0
50.0
ST1 0.0
0.0
ST2 -50.0
50.0
SET -25.0
25.0
(ST1+ST2)
SET=
2
Compound
1 kPa
0.1 kPa
500
50.0
0
-50.0
500
50.0
0
-50.0
0
-50.0
500
50.0
0
-50.0
500
50.0
500
50.0
0
-50.0
500
-50.0
0
50.0
0
-50.0
500
50.0
250
0.0