1. Before installing the wireless sensors, keep them
all near the Water Control Panel. Ensure the
sensors have batteries installed or are plugged into
a standard outlet nearby for adding into the system.
Valve must be open for programming where the
display reads "WATERCOP NORMAL".
2. On the Water Control Panel, press the "MODE"
button twice waiting a few seconds between each
button press until the display reads "DEVICE ADD /
PRESS NEXT
".
3. Press "CLOSE", which is indicated by the "NEXT
to put the Water Control Panel into add mode. The
display should read, "DEVICE ADD / DEV#_ ID=".
4. Take one sensor and short the probe to add the
sensor into the system. For Dual Sensors, only one
probe needs to be shorted to add the sensor into
the system. For Temperature Sensors, short the
moisture probe rather than the temperature sensing
probe.
5. Once the sensor has been added into the system
(which is indicated by the Water Control Panel
beeping and reading "DEVICE STATUS / SEN#__
SHORT1") wait until the display reads "DEVICE
STATUS / SEN# __ OK!".
6. Press "MODE" once to go back to the "DEVICE
ADD" display. (*If time has passed and the display
reads "WATERCOP NORMAL"; go back to step 2.)
ON
MAIN WATER
CONTROL
OFF
RJ45 Interface
SmartConnect
or wall switch
Power Supply
Note polarity striped wire
is attached to +12V terminal
WPC & WPCH
1
2
(20' Cable)
WPACT12V Actuator
1 Black
4 Brown or Yellow
5 White
2 Red
3 Green
Blue wire is not used
7. Repeat steps 3-6 for each sensor to add them all
into the system.
8. At the same time, be sure to number them
according to the order they are added into the
system. You'll need this to record them in the
Sensor Location Log (included) when you put
them in location.
9. When all of the sensors have been added into the
system, you are ready to test them.
10. Test the sensors by individually getting them wet
and waiting until the alarm goes off and closes
"
the valve.
KEEP FINGERS AND OTHER OBJECTS
AWAY FROM VALVE TO AVOID INJURY.
11. Silence the Water Control Panel by pressing any
button once AFTER the valve has fi nished closing.
12. Remove the source of wetness from the sensor
probe and dry it off completely.
13. Wait until the display reads "!ALARM! SEN#__ OK".
14. Press the "OPEN" button to open the valve and
continue.
15. Repeat steps 10-14 for each sensor probe.
16. Now you can install the wireless sensors following
the "Installing the Wireless Sensors" and "Placement
of Wireless Sensors" sections of the Instruction
Manual to properly install the sensors.
B
E
1
2
3
4
5
6
1
2
1
2
1
2
REMOTE VALVE
12V RLY
ALARM TROUBLE
3
4
5
6
1
2
1
2
REMOTE VALVE
12V RLY ALARM TROUBLE
12 VDC Signal
water is off for use with remote relay
Hardwired Sensor
(10' cable) attached here
C
1
2
when the unit displays