Connections
Caution
: Refer to the 'specifications' for checking the power supply and control output.
■ LE4S
RESET
4
5
6
START
3
2
7
INHIBIT
1
8
SOURCE
■ LE4SA
• Output operation mode
: OND / OND.2 / FLK / FLK1 / INT / TWN / TWN.1
(TWN, TWN.1 mode: time limit 2c fixed)
4
5
3
6
2
7
1
8
SOURCE
Specifications
Model
LE4S
Function
MULTI time, MULTI operation
Display method
LCD (Backlight)
Return time
≤ 100 ms
Time operation
Signal ON Start
Input signal
START, INHIBIT, RESET
Min. signal width
≈ 1, 20 ms
Short-circuit impedance: ≤ 1 kΩ
Short-circuit residual voltage
No-voltage input
: ≤ 0.5 VDCᜡ
Open-circuit impedance: ≥ 100 kΩ
Control output
Relay
Contact type
Time limit SPDT (1c)
250 VACᜠ 5 A,
Contact capacity
30 VDCᜡ 5 A resistive load
Repeat
Power ON Start
SET
: ≤ ± 0.01% ± 0.05 sec
Error
Signal ON Start
Voltage
: ≤ ± 0.005% ±0.03 sec
Temp.
Approval
ᜢ ᜧ ᜫ
Unit weight
≈ 98 g
Model
LE4S
Power supply
24 - 240 VACᜠ ± 10% 50 / 60 Hz, 24 - 240 VDCᜡ ± 10%
Power consumption
AC: ≤ 4.5 VA, DC: ≤ 2 W
Insulation resistive
100 MΩ (500 VDCᜡ megger)
Dielectric strength
2000 VACᜠ 50 / 60 Hz for 1 min
Noise immunity
± 2 kV square-wave noise by noise simulator (pulse width 1 ㎲)
0.75 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in each X,
Vibration
Y, Z direction for 1 hour
0.5 mm double amplitude at frequency of 10 to 55 Hz (for 1 min) in each X,
Vibration (malfunction)
Y, Z direction for 10 min
Shock
300 m/s
(≈ 30 G) in each X, Y, Z direction for 3 times
2
Shock (malfunction)
100 m/s
(≈ 10 G) In each X, Y, Z direction for 3 times
2
Mechanical: ≥ 10,000,000 operations
Relay life cycle
Electrical: ≥ 100,000 operations
Ambient temperature
-10 to 55 ℃, storage: -25 to 65 ℃ (no freezing or condensation)
Ambient humidity
35 to 85 %RH, storage: 35 to 85 %RH (no freezing or condensation)
• Output operation mode
: Y -∆ (Time limit 2c fixed)
• Use the A contact.
4
5
3
6
∆
Y
2
7
1
8
SOURCE
LE4SA
Power ON Start
-
-
Time limit DPDT (2c),
Time limit SPDT (1c) +
Instantaneous SPDT (1c)
(depends on operation mode)
250 VACᜠ 3 A,
30 VDCᜡ 3 A resistive load
≤ ± 0.01% ± 0.05 sec
LE4SA
AC: ≤ 4 VA, DC: ≤ 1.6 W
Time Setting
■ Setting method
• Be aware that the time is progressing when you set the time.
• If no key is pressed over 60 sec, returning to RUN mode and not storing the setting value.
1. In the parameter setting, set the output operation mode.
2. In RUN mode, press [◀] key to enter the time setting mode.
3. The last digit flashes at the time setting display part.
4. Set the time.
[◀] key: shift the setting digit, [▲] key: shift the flashing position, increasing time
5. Press [MD] key to complete the setting and return to RUN mode.
■ Setting example
• Output operation mode FK, FK1
Time progressing
Time setting
Mode
display part
display part
RUN mode
-
-
tOFF
00m 01s
tOFF
01m 20s
Setting mode
tON
00m 01s
tON
03m 57s
Input Connections (LE4S)
When wiring, make sure that the power and the signal input terminals are non-insulated.
■ No-voltage (NPN) input
• Solid-state input
Sensor
(NPN open collector output)
LE4S
START
RESET
INHIBIT
Q1
0 V
Q1-2: operates when it is ON.
• Contact input
LE4S
START
RESET
S1
INHIBIT
S2
S3
0 V
Use reliable contact enough to flow 5 VDCᜡ 1 mA
Q1-2, S1-3: operates when it is ON.
Description
Press [◀] key to enter the time setting
Flashing: the last number
Set the time via [◀], [▲] key
Press [MD] key to complete the setting
and progress the next time setting
Flashing: the last number
Press [MD] key to complete the setting
and return to RUN mode
Sensor
(NPN output)
LE4S
START
R
L
RESET
INHIBIT
Q2
0 V