Autonics ADIO-PN Instrukcja obsługi produktu - Strona 5
Przeglądaj online lub pobierz pdf Instrukcja obsługi produktu dla Systemy wejścia/wyjścia Autonics ADIO-PN. Autonics ADIO-PN 10 stron. Remote i/o boxes (profinet)
Również dla Autonics ADIO-PN: Instrukcja obsługi produktu (10 strony)

Unit Descriptions
1 2
4
5
6
7
2
01. Grounding hole
02. Mounting hole
03. Insertion part for the name plate
04. Ethernet port
05. Power supply port
06. PDCT port
07. I/O port
08. Rotary switches
09. Status indicator
10. I/O port indicator
Installation
■ Mounting
01. Prepare a 昀氀at or metal panel in the enclosure.
02. Drill a hole to mount and ground the product on the surface.
03. Turn o昀昀 all power.
3
04. Fix the product using M4 screws in the mounting holes.
Tightening torque: 1.5 N m
4
5
8
9
M4
10
■ Grounding
Be sure to use a cable with low impedance and as short as possible for
connecting the housing to the product.
01. Connect the grounding strap and M4×10 screw with washer.
02. Fix the screw in the grounding hole.
Tightening torque: 1.2 N m
M4