Autonics ARD-AI04 Podręcznik - Strona 10
Przeglądaj online lub pobierz pdf Podręcznik dla Systemy wejścia/wyjścia Autonics ARD-AI04. Autonics ARD-AI04 10 stron. Devicenet remote i/o analog, terminal block type
Również dla Autonics ARD-AI04: Instrukcja obsługi produktu (4 strony)
4) Analog Status
Analog Status is assigned as Produced I/O data by Configurator or Explicit message.
● Assembly Instance ID: 105
● Analog Status
Bit 0: Low Alarm (LL)
Bit 1: Low Warning (L)
Bit 2: Pass Signal (Nomal)
15
Analog Status of Input point 1
Analog Status of Input point 3
5) Analog Data1+Analog Data2
Analog Data 1 + Analog Data 2 is assigned as Produced I/O data by Configurator or Explicit message. By property setting,
assignment is available as Analog Input Value, Peak Value, Bottom Value.
● Assembly Instance ID: 106
● Setting range: 0 to 2 (Analog Input Value: 0, Peak Value: 1, Bottom Value: 2)
● Data type: Word, Data size: 8Word
15
Assigned value to Analog Data 1 of Input point 0
Assigned value to Analog Data 2 of Input point 0
Assigned value to Analog Data 1 of Input point 1
Assigned value to Analog Data 2 of Input point 1
6) Analog Status+Generic Status
Analog Status + Generic Status is assigned as Produced I/O data by Configurator or Explicit message.
● Assembly Instance ID: 107
15
Analog Status of Input point 1
Analog Status of Input point 3
-
7) Analog Data+Analog Status
Analog Data 1 + Analog Status is assigned as Produced I/O data by Configurator or Explicit message. By property setting,
assignment is available as Analog Input Value, Peak Value, Bottom Value.
● Assembly Instance ID: 108
● Setting range: 0 to 2 (Analog Input Value: 0, Peak Value: 1, Bottom Value: 2)
● Data type: Byte, Data size: 12Byte
15
Assigned Low Byte at Analog Data 1 of Input point 1
Analog Status of Input point 1
Assigned Low Byte at Analog Data 1 of Input point 3
Analog Status of Input point 3
Cautions during Use
1. Follow instructions in 'Cautions during Use'. Otherwise, it may cause unexpected accidents.
2. 24VDC power supply should be insulated and limited voltage/current or Class 2, SELV power supply device.
3. Keep away from high voltage lines or power lines to prevent inductive noise.
In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input
signal line.
Do not use near the equipment which generates strong magnetic force or high frequency noise.
4. This unit may be used in the following environments.
①Indoors (in the environment condition rated in 'Specifications')
②Altitude max. 2,000m
③Pollution degree 2
④Installation category II
DeviceNet Analog Remote I/O
●Data type: Byte, Data size: 4Byte
Bit 3: High Warning (H)
Bit 4: High Alarm (HH)
Bit 5: Broken Wire
● Default: 0
0
15
Assigned value to Analog Data 1 of Input point 2
Assigned value to Analog Data 2 of Input point 2
Assigned value to Analog Data 1 of Input point 3
Assigned value to Analog Data 2 of Input point 3
● Data type: Byte, Data size: 5Byte
● Default: 0
Assigned value to Analog Data 1 of Input point 0
Assigned High Byte at Analog Data 1 of Input point 1
Assigned value to Analog Data 1 of Input point 2
Assigned High Byte at Analog Data 1 of Input point 3
Bit 6: Under Range
Bit 7: Over Range
Analog Status of Input point 0
Analog Status of Input point 2
Analog Status of Input point 0
Analog Status of Input point 2
Generic Status
Analog Status of Input point 0
Analog Status of Input point 2
SENSORS
CONTROLLERS
0
MOTION DEVICES
SOFTWARE
0
(J)
Temperature
Controllers
(K)
SSRs
(L)
Power
Controllers
0
(M)
Counters
(N)
Timers
(O)
Digital
Panel Meters
(P)
Indicators
0
(Q)
Converters
(R)
Digital
Display Units
(S)
Sensor
Controllers
(T)
Switching
Mode Power
Supplies
(U)
Recorders
(V)
HMIs
(W)
Panel PC
(X)
Field Network
Devices
X-33