3.Flashing parameter in LCD display could be changed by pressing ARROW button.
Type of refrigerant selection increment goes forward in single way, such as R1->
R2->R3 Long press ARROW button can change selection direction.
4.Short press SETTING button to switch parameter selection.
5.When all parameters are set, long press SETTING button to save selected item.
6.In case FUNCTION button is pressed accidently in the process of setting
parameters, instrument will opt out and cancel all previous set items.
7.Common Problems
7.1 Low Battery Power Supply
Instrument includes low battery indication of one battery sign at the top left corner in
LCD display. When it displays, batteries should be replaced on time to obtain
accurate test reading.
7.2 Damaged Hose or Valve Stem
Please check pipe fittings and hose before test. As long as something wrong is
visible, please replace it immediately to avoid any accidence.
7.3 Failure of Refrigerant Filling
There is a valve core in the refrigerant inlet of the system. When connecting
instrument to system, pay attention to the two terminals of the hose.
Connect one terminal with a core to the refrigera-
-tion system, while another terminal without a core to the instrument.
7.4 Potential Leak Points
Every hose terminal comes with a nylon pad with a certain service life. Please
replace it when it is overused or flawed.
Check refrigeration system's pipes and other connectors.
8. Glossary
Saturation
The state of saturation is the coexistence of a refrigerant in a liquid and gas state.
Condensation Temperature
In the condenser, the refrigerant is condensed by the high-temperature gaseous
refrigerant to the temperature of the liquid refrigerant, that is, the saturation
temperature under condensing pressure.
Evaporation Temperature
In the evaporator, the refrigerant evaporates from the liquid refrigerant to the
temperature of the gaseous refrigerant, that is, the saturation temperature under
evaporation pressure.
Degree of Subcooling and Superheat
Subcooling: condensing temperature - condensing outlet temperature.