12
MODBUS
INPUT REGISTERS
Description
Dip switch 1 status
Dip switch 2 status
Room temperature sensor
Ti1 temperature sensor
Ti2 temperature sensor
Error code
Fan speed status
Mode status
Setting temperature status
Room temperature in wall pad status
Room temperature in main PCB status
Unit type
EC motor 1#RPM
EC motor 2#RPM
18
Address
400000
400001
400002
400003
400004
400005
400006
400007
400008
400009
400010
400011
400012
400013
All copying, even partial, of this manual is strictly forbidden
Type
Remark
R
R
R
R
R
Bit0= Room temperature sensor error
Bit1= Ti1 temperature sensor error
Bit2= Ti2 temperature sensor error
Bit3= Float switch error
Bit4= Indoor coil low temperature protection
Bit5= Indoor coil over heat protection
Bit6= Reserved
Bit7= Electrical heater failure
R
Bit8= Motor1 error
Bit9= Motor2 error
Bit10= System parameters error
Bit11= Reserved
Bit12= Reserved
Bit13= Reserved
Bit14= Reserved
Bit15= Reserved
Low=04(H)
R
Medium= 02(H)
High= 01(H)
Cooling mode= 01(H)
Dehumidify mode= 02(H)
R
Fan mode= 04(H)
Heating= 08(H)
R
Testing only
R
R
4-pipe= 03, 2-pipe= 02
R
This setting is configured by dip switch
R
R
FC66003740 - Rev 01