T208 Series
Table 1. Body Sizes, End Connection Styles and Maximum Allowable Inlet (Casing) Pressures
BODY SIZE
In.
DN
3/4 or 1
20 or 25
CF8M/CF3M Stainless steel
1. All flanges are welded. Weld-on flange dimension is 14 in. / 356 mm face-to-face.
2. Pipe nipples and flanges are 316 Stainless steel for flanged body assemblies.
CONTROL PRESSURE RANGE
In. w.c.
mbar
2 to 7
5 to 17
(1)(2)
(1)(2)
3 to 13
7 to 32
(1)(2)
(1)(2)
10 to 26
25 to 65
0.9 to 2.5 psig
62 to 172
1.3 to 4.5 psig
90 to 310
3.8 to 7 psig
0.26 to 0.48 bar
1. To achieve the published control pressure range, the spring case must be installed pointing down.
2. Do not use Fluorocarbon (FKM) diaphragm with this spring at diaphragm temperatures lower than 60°F / 16°C.
Installation
▲
WARNING
Personal injury, property damage,
equipment damage or leakage due to
escaping gas or bursting of pressure-
containing parts may result if this
regulator is overpressured or installed
where service conditions could exceed
the limits given in the Specifications
section (page 2) or where conditions
exceed any ratings of the adjacent
piping or piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate
code, regulation or standard) to prevent
service conditions from exceeding limits.
Additionally, physical damage to the
regulator could cause personal injury or
property damage due to escaping gas.
To avoid such injury or damage, install
the regulator in a safe location.
1. Only personnel qualified through training and
experience shall install, operate and maintain
a regulator. For a regulator that is shipped
separately, make sure there is no damage to or
debris in the regulator. Also ensure that all tubing
and piping are clean and unobstructed.
4
END CONNECTION
BODY MATERIAL
Gray cast iron
WCC Carbon steel
NPT, CL150 RF, CL300 RF,
LCC Carbon steel
or PN 16/25/40 RF
(2)
Table 2. Control Pressure Ranges and Spring Information
SPRING PART NUMBER
1B653827052
1B653927022
1B537027052
1B537127022
1B537227022
1B537327052
MAXIMUM ALLOWABLE INLET (CASING) PRESSURE
STYLES
(1)
NPT
SPRING WIRE DIAMETER
SPRING COLOR
In.
Red
0.085
Unpainted
0.105
Yellow
0.114
Green
0.156
Light blue
0.187
Black
0.218
2. Install the regulator using a straight run of pipe the
same size or larger as the regulator body. Flow
through the regulator body is indicated by the
flow arrow attached to the body. If a block valve
is required, install a full flow valve between the
regulator and the blanketed vessel. For proper
operation, the regulators should be installed with
the spring case barrel pointed down. Key numbers
referenced in this section are shown in Figures 4,
5 and 6.
A regulator may vent some gas to
the atmosphere. In hazardous or
flammable gas service, vented gas may
accumulate and cause personal injury,
death or property damage due to fire or
explosion. Vent a regulator in hazardous
gas service to a remote, safe location
away from air intakes or any hazardous
area. The vent line or stack opening
must be protected against condensation
or clogging.
3. To keep the vent assembly (key 26) from being
plugged or the spring case (key 3) from collecting
moisture, corrosive chemicals or other foreign
material, point the vent down or otherwise
protect it. The diaphragm casing (key 4,
Figure 6) may be rotated in order to obtain
desired positioning.
psig
35
75
SPRING FREE LENGTH
mm
In.
2.2
3.63
2.7
3.75
2.9
4.31
4.0
4.06
4.8
3.94
5.5
3.98
▲
WARNING
bar
2.4
5.2
mm
92.2
95.3
109
103
100
101