IRM-S04DI Intelligent Digital Input Sensor
With Phoenix Ports User Manual
1 Overview
IRM-S02TH intelligent digital input sensor with phoenix ports (sensor for short)
is used to measure 4 routes digital input (such as infrared, smoke, door status
and water). It supports MODBUS protocol through RJ45 port in RS-485 mode
to configure and collect data. It is applicable for indoor sites which need digital
signal control such as communication rooms and IT data centers.
1.1 Product Introduction
1.1.1 Appearance and Ports
The sensor's appearance and ports are shown in the following figure.
12345678
RJ45 port
LCD display panel
Alarm indicator
Phoenix port 1
1 2 3 4
Phoenix port 2
RJ45 port
Left view
Size (height × width × depth): 97mm × 44mm × 22mm
1.1.2 RJ45 Port
Two RJ45 ports are used in the electric connection of the sensor for power
supply, communication and equipment connection in series. The definition of
RJ45 ports is shown in the following table.
Pin
Pin1 and Pin2
Pin3 and Pin6
Definition
+12V/24V
1.1.3 Phoenix Port
Four phoenix ports are used to connect 4 routes digital equipment. The
sensor can measure and display whether any equipment is connected and its
status. The phoenix ports also supply +12V/24V power supply, which is the
same as the input power supply of the sensor, to the connected equipment.
The pin definition of the phoenix ports is shown in the following table.
Pin
Pin1
Definition
GND
Equipment detection
1.1.4 DIP Switch
The DIP switch is used to set sensor address and connected equipment type
to communicate with upper equipment through MODBUS protocol. The
sensor address is composed of group number and serial number within the
group. The DIP1 ~ DIP4 are used to set the group number; The DIP5 are
used to set the serial number within the group; The DIP6 is used to set the
type of connected equipment. For example, the sensor address of 70 is set as
shown in the following figure, among which 0111 means group number 7; 0
means serial number 0 within the group and 1 means that the type of
connected equipment is user customized equipment.
0 1 1 1 0 1
Note: 1. DIP switch in the ON position means 1,
1 2 3 4 5 6
DIP
ON
OFF: Fixed
Group Num
ON: User
The settings of DIP1 ~ DIP4 are listed in the following table.
DIP1 ~
DIP1 ~
Group
Group
DIP4
DIP4
0 0 0 0
0
0 1 0 0
0 0 0 1
1
0 1 0 1
0 0 1 0
2
0 1 1 0
0 0 1 1
3
0 1 1 1
The settings of DIP5, DIP6 are listed in the following table.
DIP5
Num
0
0
1
1
1.1.5 LCD Display Panel
The LCD display panel (as shown in the following figure) can display sensor
address and measured data in real time. The four numbers from left to right in
the data area means the status of input digital 1, 2, 3 and 4 respectively.
BOM 编码 31011980
DIP switch
ALARM
Phoenix port 4
Digital Input Sensor
IRM-S04DI
Phoenix port 3
Front view
Right view
Weight: about 100g
Pin4 and Pin5
Pin7
NC
GND
D+
Pin 2
Pin 3
Signal
input
or it means 0;
2. The sensor address cannot be set as 00,
which is the broadcast address.
DIP1 ~
DIP1 ~
Group
DIP4
DIP4
4
1 0 0 0
8
1 1 0 0
5
1 0 0 1
9
1 1 0 1
6
1 0 1 0
A
1 1 1 0
7
1 0 1 1
b
1 1 1 1
DIP6
Connected equipment type
0
Fixed equipment
1
User customized equipment
Measured data
Sensor address
1.1.6 Alarm Indicator
When measured digital level is the same as configured digital level
correspondingly, the alarm indicator flashes; or the indicaor extinguishes.
1.2 Technical Specification
Operating voltage: 9Vdc ~ 28Vdc; Power consumption: 0.2W
2 Installation
2.1 Environment Requirement
1. Operating environment should be free of conductive dust and
metal-corrosive & insulation-breaking gases.
2. Avoid using the sensor in watery or foggy places.
3. Keep a clearance of more than 20mm around the sensor's airway to
ensure ventilation inside and outside of the sensor.
4. Operating temperature: -10°C ~ +50°C; Storage temperature: -30°C ~
+70°C; Humidity: 5% ~ 95%RH (non-condensing).
2.2 Unpacking Inspection
Unpack the sensor and visually inspect the sensor's appearance. If any
damage is found, please contact the carrier immediately.
Check against the consignment list to make sure the sensor and accessories
are complete and correct.
2.3 Mechanical Installation
Three modes are available for the sensor's mechanical installation. The
installation accessories and modes are shown in the following figure.
0
Back installation hole
Pin8
D-
Back installation hole
Mode one: Insert the magnet pothook into the sensor's back installation hole,
and the sensor can absorb on iron surface.
Mode two: Insert the L pothook into the sensor's back installation hole, and
hang the pothook in the square hole of rack's column with care.
Pin 4
Mode three: Insert the T pothook into the sensor's back installation hole,
+12V/24V
insert the bulge of the T pothook into the installation slot of the rack's basic
frame, and rotate the sensor 90 degree clockwise with care.
Note
The sensor can not only be installed through the three kinds of accessories
above, but also can hang on fixed screws directly through the installation hole.
2.4 Cable Connection
1. Insert one end of the standard straight network cable into the sensor's
RJ45 port, and insert the other end into the sensor appropriative port of upper
equipment or sensor in series.
2. Refer to 1.1.3 Phoenix Port for port definition, and connect cables as
shown in the following figure.
Door
Equipment detect
status,
water,
smoke
3 Maintenance
Group
1. To clean the sensor, you should cut off the power and use a piece of soft
C
cloth to wipe it.
d
2. Do not disassemble the sensor, or the inside subtle parts may be damaged.
E
F
Emerson Network Power Co., Ltd.
Address: No.1 Kefa Rd., Science & Industry Park, Nanshan District 518057,
Shenzhen China
Homepage: www.emersonnetworkpower.com.cn
Copyright © 2009 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to change
without notice.
Version V1.5
Note: "-" means no equipment connected
"0" means no alarm
"1" means alarm exists
Sensor
GND
Infrared
DI signal input
DI signal input
Revision date November 6, 2009
Magnet pothook
L pothook
T pothook
GND
Equipment detect
DI signal input
DI signal input
+12V/24V
BOM 31011980