Liebert Intellislot
I
NSTALL
• Locate the adapter mounting location in your Liebert equipment.
• Secure the Intellislot 485 Card with Adapter with the supplied screws.
• Connect the equipment's communication cable to the TB1 terminal
block or P1 on the card (See equipment user manual for details).
• Connect a Modbus (RS-485) cable to the TB2 terminal block.
• Connect an input power supply cable to Pins 1 & 2 on the TB3 terminal
block; Pin 1 is at the far left, and Pin 2 is the middle pin.
TB3
(P1: +)
(P2: -)
(P3: NC)
P1 is on
left end of
terminal
block.
TB2
(P1: +)
(P2: -);
P1 is at the
right side of
terminal block.
C
ONNECT THE
• Locate the blue serial configuration cable (null modem) that shipped
with the card.
• Connect the configuration cable to the DB-9 port on the card and to a
COM port on your PC.
C
ONFIGURE THE
• Use terminal emulation software, such as
HyperTerminal
tion to the card. Use the data at right to
configure the emulation software.
• Press Enter for the Main Menu.
• Select the option for 485 Network Set-
tings and press Enter to access the com-
munications settings.
• Enter 1 and press Enter.
• Select Modbus Server to enable the Modbus application.
• At the next screen, enter 3 to access the screen to set the Server ID
(the ID default is 1, but may be any number up to 255).
• Press Esc to return to the Main Menu.
• Enter X and press Enter to exit HyperTerminal, save your changes
and reboot the card.
With Adapter
Quick Start Guide
C
ABLE
C
ARD
, to open a direct connec-
485 Card
®
P1
TB1 (P1: +; P2: -); P1 is at the
right side of terminal block.
Emulation Software
Configuration
Baud Rate:
Data Bits:
Parity:
Stop Bits:
Flow Control: None
DB-9
Port
9600
8
None
1