Cor HRVCRSVU1157 Instrukcja instalacji - Strona 13

Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Wentylator Cor HRVCRSVU1157. Cor HRVCRSVU1157 17 stron. Heat recovery ventilator

Cor HRVCRSVU1157 Instrukcja instalacji

BALANCING THE UNIT

What you need to balance the unit
S A magnehelic gauge capable of measuring 0 to 1 inch of water
(0 to 249 Pa) and 2 plastic tubes.
S The balancing chart of the unit.
Fig. 28 - Magnehelic gauge
Preliminary stages to balance the unit
S Seal all the unit ductwork with tape. Close all windows and
doors.
S Turn off all exhaust devices such as range hood, dryer and
bathroom fans.
S Make sure the balancing dampers are fully open by setting both
damper balancing tools completely vertical.
S Make sure all filters are clean (if it is not the first time the unit is
balanced).
Fig. 29 - Damper balancing tool

Balancing procedure

1. Set the unit to high speed.
NOTE: Make sure that the furnace/air handler blower is
ON if the installation is in any way connected to the duct-
work of the cold air return. If not, leave furnace/air handler
blower OFF. If the outside temperature is below 0_C/32_F,
make sure the unit is not running in defrost while balancing.
(By waiting 10 minutes after plugging the unit in, you are
assured that the unit is not in a defrost cycle.)
2. Place the magnehelic gauge on a level surface and adjust it
to zero.
3. Connect tubing from gauge to EXHAUST air flow pressure
taps (the ones with arrows, see insets in illustration beside).
Be sure to connect the tubes to their appropriate high/low
fittings. If the gauge drops below zero, reverse the tubing
connections.
4. Note the CFM value from balancing chart located on unit.
5. Repeat steps 3 and 4, but to FRESH air flow pressure taps.
A11217
6. Match highest CFM value to lowest by adjusting the balan-
cing damper corresponding to the highest value.
7. Secure both dampers in place with a fastening screw (in-
cluded).
8. Write the required air flow information on a label and stick
it near the unit for future reference (date, maximum speed
air flows, your name, phone number and business address).
NOTES:
A11218
1. Use conversion chart provided with the unit to convert mag-
nehelic gauge readings to equivalent cfm values.
2. The unit is considered balanced even if there is a difference
of 10 cfm (or  5 l/s or 17 m
flows.
13
Stale air flow
Fresh air flow
Fig. 30 - Balancing procedure
3
/h) between the two air
A11220