Galvin Engineering CliniMix CP-BS WM-TMVPMB Instrukcja instalacji produktu - Strona 14

Przeglądaj online lub pobierz pdf Instrukcja instalacji produktu dla Produkt hydrauliczny Galvin Engineering CliniMix CP-BS WM-TMVPMB. Galvin Engineering CliniMix CP-BS WM-TMVPMB 18 stron. Hob mounted thermostatic progressive basin mixer - lever

Galvin Engineering CliniMix CP-BS WM-TMVPMB Instrukcja instalacji produktu
5. Disinfection Process
Turn the tap handle anti-clockwise fully.
Hot water will now pass thru the cold inlet and into the thermostatic mixing chamber (exiting the mixed outlet).
Run water for the correct disinfection time as shown in Table 4.
Temperature
Disinfection
60 degrees
30 Minutes
65 degrees
15 Minutes
70 degrees
10 Minutes
Table 4 - G
uide to disinfection temperatures v/s time
To avoid scalding/burning, keep clear of the mixed outlet.
6. Cool Down Unit
This unit becomes very hot during operation. Extreme care should be taken when reversing hoses.
Ensure the unit is cool to touch before reassembly.
 After the required disinfection time, turn the tap handle to the off position.
 Repeat steps 1 to 3 and return the hoses to their original position.
 Check tap for correct operation.
14
Version 2, 29 May 2020, 14 of 18