Merlin 1000S+
2.6
This terminal is for remote emergency shut-off buttons and detailed on the
circuit board as [EM REMOTE].
This is linked out as a factory setting.
Remote emergency shut-off buttons should be volt free and wired to the
Merlin 1000S+ using a plenum security cable, white, 18/2 (18AWG 2
conductor), stranded, CMP or similar.
2.7

GAS DETECTOR

These connections can be wired to a Merlin gas detector (LPG, natural
gas or carbon monoxide).
If no detector is being used leave the link in between the "
Refer to your gas detector guide for further information.
2.9

CO2 MONITOR

This terminal can be connected to a CO
the event of a high concentration of CO
If no CO2 monitor is connected, the panel will 'beep' upon power up
and the CO2 LED will flash 3 times to indicate that this terminal has been
disabled.
Refer to your CO
monitor guide for further information.
2
2.10
This is a permanent 12v DC output when there is power at the panel and
can be used to create a relay switch with the BMS relay output.
Contact your supplier for more information.
Rev: 06
05-19

EM REMOTE

2.8
FS1/2/3
This terminal switches when the key is turned on and off.
This can be linked to a fan switch (supplied separately) which can provide
power to the fans when the control panel is switched on.
2
2
12v DC
".
monitor to shut off the system in
.
User Guide
5