NOTE: In some installations, certain types of tapware devices such as flick mixers and solenoid valves
are used. The water pressure may be seen to spike outside that recommended for the valve, during
rapid shut off conditions with these types of devices. Even if the spike only lasts a split second it is still
considered to be outside the operating conditions and may cause the valve to operate incorrectly. In the
event that this does occur, measures must be taken to control the spike, such as the installation of an
inline pressure reducing valve directly before the valve inlets.
To ensure that the mixing valve operates correctly, it is necessary that the pipe-work is thoroughly flushed with
clean water before the valve is installed. This will remove any physical contaminants from the pipe-work,
ensuring trouble-free operation. During the flushing procedure, care should be taken to prevent water damage
occurring to the surrounding area.
t is a requirement of AS3500.4.2 that " ach thermostatic mixing valve shall have an isolating stop tap/valve,
line strainer and non-return valve fitted to the hot and cold water supply lines". The inlet fittings supplied with
each TMV will ensure this requirement is met. If the CliniMix
installed without the supplied inlet control valves then it will be necessary to install a separate isolating valve,
non-return valve and strainer to both inlets to the valve.
Strainers must be fitted to prevent any particulate contamination from entering the valve. These strainers
should be 60 mesh stainless steel (0.250mm). Isolating valves are required so that the water supply to the valve
can be isolated when servicing is required. Non-return devices must also be fitted to both the hot and cold inlets
to prevent cross-contamination.
Ensure that the test plugs in the top of the inlet fittings are tight.
The valve should be installed so it can be easily accessed for maintenance or servicing.
During installation or servicing, heat must not be applied near the mixing valve or inlet fittings, as this will
damage the valve and inlet fittings internals. Failure to comply with this requirement will damage the valve and
fittings. It will put the user at risk and it will void the warranty of the valve.
®
Note: The CliniMix
Thermostatic Progressive Mixing Valve is intended mainly for use in applications
with set temperatures below 45° Celsius. When installed at higher set temperature, the performance
may be less than specified in AS4032.4. In such situations consideration should be given to the
question of whether an alternative device, i.e. a tempering valve approved to AS4032.2 would provide a
greater margin for safety in reducing scalding accidents.
8.0

OPERATION

As the handle is rotated anti-clockwise from the off position the
delivered water progresses from cold through warm to the pre-set
maximum temperature of approximately 41°C
®
Progressive Thermostatic Mixing Valve is to be
FF
8
st
Version 2.1, 31
July 2020 , 8 of 18