AGS Merlin 1000SW+ Instalacja, obsługa i konserwacja - Strona 9
Przeglądaj online lub pobierz pdf Instalacja, obsługa i konserwacja dla Kontroler AGS Merlin 1000SW+. AGS Merlin 1000SW+ 12 stron. Gas, electric & water isolation controller
Również dla AGS Merlin 1000SW+: Instrukcja instalacji i obsługi (16 strony)
Installation & Operation Manual
Operation
Initial Power Up
All services can be turned on or off within 10 seconds only of the key switch being turned on. After 10 seconds, all utility
buttons will be disabled. The user must turn the key off and back on to adjust any services.
On connecting mains power, an LED on the front of the panel (AGS Logo) will illuminate red.
Turn the key switch to on position.
1.
Gas, Electric and Water LEDs will flash for 10 seconds.
2.
Press relevant service button to turn required utility on.
3.
LED Indicators
•
Gas
When the key switch is turned on, the LED will illuminate.
•
Electric
When electric service is turned on, the Electric LED will illuminate.
ON = Electric on / FLASHING = Electric Off, Electric button enabled / OFF = Electric Off, Electric button disabled.
•
Water
When water service is turned on, the Water LED will illuminate.
ON = Water on / FLASHING = Water Off, Water button enabled / OFF = Water Off, Water button disabled.
•
N/A
Testing
•
N/A
Test Fail
•
N/A
Pressure Low
•
Timeout
Under normal working conditions this LED is off. This LED will illuminate AMBER when auto-shut down
has occurred.
OFF = OK / ON = Auto-shut down activated
•
EM Stop
If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate
AMBER and the gas will be turned off and the fans switch (if a fan switch is connected). The EM Stop
button must be reset before restarting the system. The emergency shut off button(s) will cut off the gas
supply, electrics, and fans (if connected) when activated.
•
CO2/ Gas Detected
Under normal working conditions this LED is off. If the external Merlin detector connected detects gas
this will show RED, and the gas valve will turn off.
•
CO
High
2
Under normal working conditions this LED is off.
If the concentration of CO2 in the air is at alarm level (relevant detector required), the LED will show RED
and the Gas valve will turn off.
Rev: 15
08-22
OFF = OK / ON = Gas detected.
OFF = OK / ON = the concentration of CO2 is at alarm level.
ON = Gas On / OFF = Gas Off
OFF = OK / ON = Emergency Shut-Off button activated.
Merlin 1000SW+i