AGS Parksafe Control Panel Instrukcja instalacji i obsługi - Strona 5

Przeglądaj online lub pobierz pdf Instrukcja instalacji i obsługi dla Kontroler AGS Parksafe Control Panel. AGS Parksafe Control Panel 16 stron. Ventilation control panel
Również dla AGS Parksafe Control Panel: Instrukcja instalacji i obsługi (16 strony), Instalacja, obsługa i konserwacja (16 strony), Instrukcja instalacji, obsługi i konserwacji (20 strony)

AGS Parksafe Control Panel Instrukcja instalacji i obsługi
Installation & Operation Manual
1. POWER/ LINE IN
100-120V AC single phase mains power should be supplied to the [POWER/LINE IN] connector
using a 3 core cable and fused at 3A. On connecting the mains supply to the panel the power
LED indicator will light up – this is located on the front cover (AGS Logo).
2. OUTPUT 1 RELAY
This relay output switches when any external AGS gas detectors reach 'pre-alarm' status.
The 0-10V output will send 5V to ventilation systems.
OUTPUT 2 RELAY
This relay output switches when any external AGS gas detectors reach 'alarm' status.
The 0-10V output will send 10V to ventilation systems.
ALARM RELAY
This relay output switches when any external AGS gas detectors reach 'alarm' status for longer
than the selectable 1-5 minute delay time following 'Output 2'. Selectable in the settings menu.
The Parksafe panel will sound its internal buzzer to alert the user.
DAMPER RELAY
This relay output can switch together with either OUTPUT 1, OUTPUT 2 or ALARM relays. Selectable
in the settings menu.
3. DETECTOR CHAIN
12-24V power and Modbus communication data is wired to AGS Parksafe gas detectors.
Up to 16 detectors can be connected to the Parksafe panel and chained up to approx. 500
yards from the panel (this varies depending on chain configuration, wire type and condition).
For more information refer to your AGS Parksafe detector manual.
4. SOUNDER/ STROBE
This relay output (24V) is for an external sounder alarm/ strobe lighting to activate on alarm.
5. 24VDC
This is a permanent 24V DC power output for external auxiliary devices.
Max output: 200mA.
6. 0-10V OUTPUT
This output can drive ventilation systems. The 0-10V output will send 5V when Output 1 relay is
activated and 10V when Output 2 relay is activated.
Under normal conditions, the output can be 0 or 2V – selectable in the settings menu.
AGS Parksafe - IOM Iss: DRAFT 3 06-20
Parksafe Control Panel
5