9. Specifications

Universal Input
Strain Gauge:
Thermocouple
Calibration:
PT100 Calibration:
DC Calibration:
Sampling Rate:
Impedance:
Sensor Break
Detection:
Thermocouple/RTD:
Isolation:
Logic Input
Input Signal:
Isolation:
350
, by means of 4 or 6 wire (6 to use internal Shunt resistor)
Bridge excitation: 10VDC ± 7% @ 45mA Max.
Bridge Sensitivity: 1.4-4mV/V
Shunt Value: From 40%to 100%
Input signal Span: -25% to 125% (Approx. -10mV to +50mV)
± 0.1% of full range, ±1LSD (±1°C for Thermocouple CJC).
BS4937, NBS125 & IEC584.
±0.1% of full range, ±1LSD.
BS1904 & DIN43760 (0.00385 / /°C).
±0.1% of full range, ±1LSD.
4 per second. (250ms)
>10M
resistive, except DC mA (5
Strain Gauge: Depending on user setting lnPF can cause input to fail
high scale or low scale reading. Reading will fail on either, Sig+ or Sig-
loss, or incorrect excitation output <0.8mA and >50mA supply.
High alarms activate for sensor break. Linear 4 to 20mA, 2 to 10V and
1 to 5V DC: Low alarms activate for sensor break.
Note: Sensor break not detectable on 0 to 20mA, 2 to 10V
and 1 to 5V DC input types.
Isolated from all outputs.
Universal input must not be connected to operator accessible circuits
if single relay outputs are connected to a hazardous voltage source.
Supplementary insulation or input grounding would then be required.
If the Logic State setting in Config Mode = CLS, Reset or Tare occurs on
an Open to Closed transition, or high (3 to 5VDC) to low (<0.8VDC)
transition.
If Logic State setting in Config Mode = OPN, Reset or Tare occurs on a
Closed to Open transition, or low (<0.8VDC) to high (3 to 5VDC))
transition.
No isolation from inputs and other outputs.
P/N: n/a
Rev: n/a
www.dynisco.com
-16-
) and V (47k ).