System On and Off
Turn the key switch to on position.
Gas and electric will flash for 10 seconds.
Press relevant service button to turn required utility on.
Turn the key switch to the off position to turn the panel off.
Please Note: All services can be turned on or off within 10 seconds of the key switch being turned on.
After 10 seconds, all utility buttons are disabled. The user must turn the key off and on to adjust services.
3.2
Emergency Shut Off
The emergency shut off button is located on the front of the panel.
There is also a facility for remote shut off buttons to be wired in series on the circuit board.
The emergency shut off button(s) will cut off the gas supply when activated.
To reinstate the system, the emergency shut off button(s) will need to be reset and the panel
restarted.
3.3
BMS Integration
The Merlin 1000S+ can be integrated with a BMS to make or break a circuit
on gas on/gas off, (valve open or valve closed).
This will tell the BMS whether or not power is being sent to the solenoid.
There is a dip-switch located on the inside facia of the panel labelled [BMS
SEL]. This is factory set to 'OFF' which signals the BMS on gas on/gas off.
When switched to 'ON', the 1000S+ will only signal the BMS on a fault, i.e.
high CO2 level detected, gas detected, emergency stop pressed, etc.
3.4
Auto shut-down / Timeout facility
The Merlin 1000S+ has an auto-shut down feature after a selected time.
There are two dip-switches located on the inside facia of the panel labelled
[TIME1] & [TIME2]. Upon installation, these can be configured to select the
required timeout/ shut-down period.
TIME 1
TIME 2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
They are factory set to 'OFF' for a 2 hour timeout.
Note: Upon timeout/auto-shut down the gas supply will be turned off.
On auto-shut down, the gas supply will be turned off.
There is a dip-switch located on the circuit board labelled [ELECTR]. They are factory set in the
'off' position. Upon installation, they can be switched to the 'on' position. This will instruct the
system to also turn off Electric and/or Water services when performing auto-shut down.
Rev: 06
05-19
Timeout Period (Hours)
2
4
8
Disabled