Majestic fireplaces PVS-1 Instrukcja instalacji i obsługi dla właściciela domu - Strona 5

Przeglądaj online lub pobierz pdf Instrukcja instalacji i obsługi dla właściciela domu dla Wentylator Majestic fireplaces PVS-1. Majestic fireplaces PVS-1 12 stron. Power venting system for use with decorative gas appliance models: nvc33vn/vp, nvc36vn/vp, nvc39vn/vp, nvc43vn/vp

Majestic fireplaces PVS-1 Instrukcja instalacji i obsługi dla właściciela domu
Installation
1. Slip Sound Reducer into flue collar and press on to
fireplace top.
2. Fasten Sound Reducer to fireplace top with four (4)
sheet metal screws supplied.
3. Continue with the power venter installation as per
instructions supplied with same.
Fig. 1 Secure sound reducer to fireplace top with four (4)
sheet metal screws.

Installation Restrictions

Sound Reducer Kit SR6
FP1417
1. Although the Power Venter can be installed any-
powervent
where in the exhaust system, it is best if it is installed
system
as close to the termination of the vent system as
front view
possible to obtain optimal appliance efficiency and to
11/24/03 djt
prevent flue gas leakage. (Fig. 2)
Anti-Vibration Sleeve
Fig. 2 It is best to install Power Venter as close to the termi-
nation as possible.
2. Power Venter must be mounted with motor shaft hor-
izontal to ensure proper operation of the fan proving
switch and to prevent motor bearing wear. (Fig. 3)
51810
4" (102 mm) Insu-
lated Flue Liner
Sound Reducer
Sheet Metal
Screws
Fireplace Top
Fireplace
FP1417
Vent Support Hangers
Spaced 36" (914mm) on
Horizontal Run
FP1418
FP1418
power vent location
11/24/03 djt
Majestic
Fireplaces Power Venting System
®
Horizontal Discharge
Motor Shaft
Vertical
Incorrect
Fig. 3 The Power Venter must be mounted with motor shaft
horizontal.
3. Power Venter housing in single wall a 6" (152 mm)
clearance must be maintained. (Fig. 4)
Combustible Material
6" (152mm)
Minimum
NOTE: 6" (152mm)
maximum clearance from
combustible must be
maintained.
Combustible Material
Fig. 4 Minimum clearance.
4. Allow for a minimum of 18" (457mm) vertical rise off
the top of the appliance before the vent makes a 90°
FP1420
Minimum clearance
elbow to the horizontal. (Fig. 5)
11/25/03 djt
5. Vent pipe transitions, where necessary, should be
gradually tapered. (Fig. 6)
6. Power Venter to vent pipe connections and all joints
on the outlet side of the Power Venter must be
sealed with high temperature silicone sealant or alu-
minum vent pipe tape to prevent flue gas leakage.
(Fig. 7)
7. The vent terminal must not be more than 20' (6m)
below the appliance's flue outlet.
Vertical Discharge
Oil Holes
FP1419
FP1419
motor views
11/25/03 djt
Power Venter
FP1420
5