When using electrical equipment, basic safety precautions should always be followed including the following:
WARNING – Read all product labels and instructions before installation.
WARNING – Turn off power before installation, inspection or removal.
WARNING – Installation and servicing should be done by qualified personnel only in accordance with the National Electrical Code and local regulations.
De-energize before opening.
WARNING – This unit provides more than one power supply connection point. To reduce the risk of electrical shock, disconnect both normal and emergency sources by turning off the
A.C. branch circuit and by disconnecting the unit connector before servicing.
WARNING – Sealed unit. Battery not replaceable. Replace entire unit when necessary.
WARNING – This unit requires an unswitched power source of 120-277VAC, 50-60Hz.
•
For use with 120-277VAC line voltage products rated 23W or less.
•
Electricians or end-users must confirm system compatibility before final installation.
•
Operates in emergency mode for 90 minutes.
•
24-hour recharge time.
•
For use in an operating environment ranging from 50°F / 10°C to 122°F / 50°C.
•
Suitable for use in damp locations.
•
Unit must be grounded.
•
Do not use outdoors.
•
Do not mount near gas or electric heaters.
•
Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.
•
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
•
Do not use this equipment for other than its intended use.
•
Use with grounded, UL Listed, damp location rated fixtures and case should be grounded.
•
The Emergency LED Driver is intended for ordinary locations and for permanent installation into one or more Listed luminaires.
CAUTION – Device has to be checked and re-activated to keep emergency function after installation
1.
Make sure the POWER IS TURNED OFF at the source to the location at which you are installing the unit.
2.
Secure the EMERGENCY LED DRIVER to the fixture or in a position in the ceiling that does not interfere with any existing hardware. Installation should comply with local
regulations.
3.
For switched power applications, make sure an unswitched line also exists in the J-box or fixture wiring compartment.
4.
Insert the flex conduit that connects to line voltage into the J-box or fixture wiring compartment and wire according to the wiring diagram below. To prevent electrical shock,
pair the unit connector last.
5.
For unswitched constant power applications (emergency only, light is off in normal condition) connect the incoming unswitched line to the unit's black wire and cap off the unit's
black/white switched line.
6.
Install the test accessory plate in a single-gang switch box (not provided) in the ceiling near the fixture and wire according to the wiring diagram below. Make sure the indicator
light and test switch are wired correctly.
7.
For testing and maintenance refer to the Test Button & Indicator Light section below.
8.
Restore power at the source and installation is complete.
LED LAMP OR FIXTURE
NEUTRAL
SWITCHED LINE
UNSWITCHED LINE
GROUND
SINGLE-GANG SWITCH BOX(NOT PROVIDED)
FOR TEST ACCESSORY PLATE AND SWITCH
www.greencreative.com - [email protected] - Tel / Fax: (866) 774-5433 -
EMERGENCY LED DRIVER INSTALLATION - WARNING
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
EMERGENCY LED DRIVER INSTALLATION
YELLOW/BLACK TO HOT (L)
YELLOW TO NEUTRAL (N)
WHITE
BLACK/WHITE
BLACK
GREEN
EMERGENCY
LED DRIVER
FIXTURE
23EMDRIVER
/ GREENCREATIVELED
/ GClightingLED
For model #: 23EMDRIVER
BLACK
BLACK
UNIT CONNECTOR
RED/WHITE
RED/WHITE
INDICATOR LIGHT
RED
RED
WHITE
TEST SWITCH
BLACK/WHITE
L, N, GROUND AND UNSWITCHED LINE COMING IN
J-BOX OR FIXTURE WIRING COMPARTMENT
/ GREEN-CREATIVE
An ILLUMUS Brand