1.9 Menu Functions
By pressing the "Next" key (arrow pointing right), the user will reach the first menu level. The following menu
options can be selected:
Edit time programme
Copy time programme
Settings
Service
The menu is selected by pressing the "Confirm" key (tick).
All settings are adjusted according to the same principle:
Change to the next/previous menu level: → / ←
Increase/reduce value or change the setting: + / -
Select setting or confirm change:
One step back:
1.9.1 Operating Modes
Manual operation When manual operation is selected, the control panel for the ventilation level setting is
also displayed. By pressing the "Ventilation stage" key, basic ventilation, ventilation level 1, ventilation level
2, ventilation level 3 and Off can be selected (the Off function is only possible when basic ventilation is
deactivated in the Service menu of the software program). The selected ventilation stage is displayed in text
field 1.
Time programme (weekly time programme) When the time programme option is selected, a clock is also
shown in the "Operating mode" control panel (top right corner). The ventilation stages are set automatically
according to the selected time programme. The active ventilation stage is displayed in the "Ventilation stage"
display.
Automatic operation When automatic operation is selected, the ventilation stages are controlled
automatically depending on the air quality. The measured air quality is shown in the display in the "Sensor"
display. "AUTO" will also display with the current ventilation stage. The sensitivity of the sensor control can
be adjusted in the "Settings" menu.
OFF (only possible when basic ventilation is deactivated) When "Off" mode is selected, the dampers will be
closed and the air discharge/supply to the service unit will be interrupted.
1.9.2 Display Light
The display light is set using the "Light" control panel (lamp symbol). In this respect, hold the key for 5
seconds. Either "Continuous display" (lamp symbol without arrow) and "Automatic deactivation after 30
seconds" (lamp symbol with arrow) can be selected.
The deactivated display can be reactivated by touching the bottom left corner of the screen.
1.9.3 Time Programme
The weekday can be selected under "Edit time programme". Select the desired weekday using the arrow
keys. Then select the time segment, set the hours and minutes, and select the desired fan speed. You can
also save other time segments (max. 6 segments per day). In addition, ventilation stage 0 (only if basic
ventilation deactivated), ventilation stage G (basic ventilation) and ventilation stage A (automatic operation)
can also be set in the time programme function.
Example:
Segment 1: 22:00 hrs, ventilation stage 1
Segment 2: 06:00 hrs, ventilation stage 2
Segment 3: 08:00 hrs, ventilation stage 1
The ventilation unit is active from 22:00 to 06:00 on ventilation stage 1, from 06:00 to 08:00 on ventilation
stage 2 and from 08:00 until the next set time segment. If no time is set, the unit will continue basic
ventilation (ventilation stage 1).