Berner AI10 Instrukcja instalacji i konserwacji - Strona 5
Przeglądaj online lub pobierz pdf Instrukcja instalacji i konserwacji dla Grzałka Berner AI10. Berner AI10 16 stron. Architectural icon air curtain
NOTE: The three wall mounting plates are identical. Two of the
wall mounting plates are attached to the back of the air curtain,
and one is attached to the wall.
3.
The mounting hardware (supplied by others) must
be capable of supporting a minimum of three times
the net weight of the Air Curtain. See Table 1.
MOUNTING WALL PLATES
B.
1.
Position wall mounting plate over the door opening
as shown in Figure 3. The plate should be centered
over the door opening.
2.
Using minimum ¼" fasteners (supplied by others),
secure the wall mounting plate to the supporting
structure. NOTE: It is acceptable to drill holes
through the plate mounted to the wall to
allow fasteners to hit a wall stud. Fasteners must
be placed within 6" of the ends of the air curtain
cabinet.
C.
ATTACHING THE AIR CURTAIN TO THE WALL
MOUNTING PLATES
1.
Raise the unit over the door (air discharge nozzle
facing down) and onto the wall mounting plates.
See Figure 5.
2.
Position the unit against the wall, slide it down so
the top wall mounting plate (attached to the unit)
interlocks with the wall mounting plate that is
attached to the wall. Add one locking screw in the
top middle of the wall mounting plate. See Figure 5.
3.
Proceed to Section V - ELECTRICAL CONNECTIONS
IV. SUSPENDED MOUNTING
NOTE: if the unit was ordered with a decorative rear
cover, the air curtain will arrive with the cover already
installed, and the wall mounting plates will not be included in
the shipment. Contact Berner if they are required.
A.
For top mounting using suspension rods, four (4) factory
installed 1/4"-20 threaded inserts are located on the top of
the unit. See Figure 6.
B.
Install 1/4"-20 threaded rods, or other suitable hardware at
a location sufficient to support the Air Curtain. The
mounting hardware (supplied by others) must be capable
of supporting a minimum of three times the net weight of
the Air Curtain. See Table 1.
C.
Attach 1/4"-20 threaded rods, or other suitable hardware
to the top mounted threaded inserts. Secure threaded rods
with locking nuts.
Proceed to Section V – ELECTRICAL CONNECTIONS
D.
V. ELECTRICAL CONNECTIONS
All electrical wiring and connections MUST be performed by
qualified personnel in accordance with the latest edition of the
National Electrical Code ANSI/NFPA No. 70 or, in Canada, the
Canadian Electrical Code, Part 1-C.S.A. Standard C22.1 and local
codes and regulations.
MAKE SURE THE CORRECT VOLTAGE AS MARKED
ON THE UNIT IS USED.
ATTACH
TO WALL
WALL
MOUNTING
BRACKETS
1/4" FASTENERS
(by others)
Figure 4 - Wall Mounting Preparation
A
LOCKING
SCREW
Figure 5 - Wall Mounting Installation
Figure 6 - Suspended Mounting
-5-
SUPPLIED 1/4-20 BOLTS
TIGHTEN TO 50 IN-LBS
LOCKING
SCREW