SR-10T Clearances (Figure 1 and Figure 2)
When facing the front of the appliance the following minimum clearances
to combustible construction must be maintained.
Left side 6 inches (152mm). Right side 6 inches (152mm).
Do not install in alcove or closet.
Rear wall 0 inches (0mm). Ceiling 24 inches (610mm).
Minimum vertical clearance from a projection above the
appliance (shelves, window sills, etc.) 14 inches (356mm).
Maximum horizontal extension of projection above the appliance
12 inches (305mm).
Floor (top surface of carpeting, tile, etc.) 2 inches (51mm).
Provide adequate clearances around air openings.
Adequate accessibility clearances for purposes of servicing and proper
operation must be provided.
24 " MIN
(610mm)
14" MIN
(356mm)
6 " MIN
(152mm)
2 " MIN
(51mm)
Figure 1 (SR-10T)
24 " MIN
(610mm)
14" MIN
(356mm)
2 " MIN
(51mm)
Figure 2 (SR-10T)
R-5210
6 "MIN
(152mm)
12" MAX
(305mm)
0" (0mm) CLEARANCE
TO REAR WALL
SR-18T Clearances (Figure 3)
When facing the front of the appliance the following minimum clearances
to combustible construction must be maintained.
Left side 6 inches (152mm). Right side 6 inches (152mm).
Do not install in alcove or closet.
Rear wall 0 inches (0mm). Ceiling 36 inches (914mm).
Minimum vertical clearance from a projection above the
appliance (shelves, window sills, etc.) 36 inches (914mm).
Floor (top surface of carpeting, tile, etc.) 2 inches (51mm).
Provide adequate clearances around air openings.
Adequate accessibility clearances for purposes of servicing and proper
operation must be provided.
36" (914mm) MIN
6" (152mm)
MIN
2" (51mm)
MIN
Figure 3 (SR-18T)
6" (152mm)
MIN
Page 5