5) Auto restart
Enable or disable automatic system restart after a power outage.
Setting Description
Yes
No
* Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, or external input device.
6) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature
sensor.
Setting Description
No
Yes
If setting value is "00",
„
room temperature is controlled by the indoor unit temperature sensor.
If setting value is "01",
„
room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
7) Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
Setting Description
A
B
C
D
8) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Setting Description
Operation/Stop mode
(Setting forbidden)
Forced stop mode
9) Indoor unit fan control for energy saving (Only cooling mode)
Enable or disable indoor unit fan control when the outdoor unit is stopped.
Setting Description
No
Yes
If setting value is "00":
„
When the outdoor unit is stopped, the indoor unit fan operates following the setting on the remote controller
continuously.
If setting value is "01":
„
When the outdoor unit is stopped, the indoor unit fan operates at very low speed intermittently.
(  . . .Factory setting)
Function Number
Setting Value
40
(  . . .Factory setting)
Function Number
Setting Value
42
(  . . .Factory setting)
Function Number
Setting Value
44
(  . . .Factory setting)
Function Number
Setting Value
46
(  . . .Factory setting)
Function Number
Setting Value
49
- (01 - 27) -
00
01
00
01
00
01
02
03
00
01
02
00
01