Power Source Requirements

Both the SPARC Enterprise T5120 and T5220 servers have two autoranging power
supplies. To ensure redundant operation of the power supplies, connect the two
power cords to separate circuits.
Server models that run on DC input power require that you build power cables and
connect to DC input power as specified in the SPARC Enterprise T5120 and T5220
Server Installation Guide.
Use the specifications only as a planning guide. For more precise power values, make
power measurements on your specific server configuration using your planned
workload. Refer to one of the following tables based on the model of your server.
SPARC Enterprise T5120 Server (4-Disk Capable) Power Specifications
TABLE 5
General Specifications
Operating input voltage range
(input voltage tolerance +/- 10%)
Maximum operating input current
Maximum operating input current
Maximum operating input power
Maximum heat dissipation
Maximum standby power
Maximum Server Configuration Specifications
Under Nominal Temperature and Voltage Conditions
(8 core, 1.6 GHz processor, with sixteen 4 GB FBDIMMs, 4 HDDs, 3 PCIe I/O cards)
Idle input power
Peak input power running SpecJBB
Minimum Server Configuration Specifications
Under Nominal Temperature and Voltage Conditions
(4 core, 1.2 GHz processor, with four 1 GB FBDIMMs, no HDDs, no PCIe I/O cards)
Idle input power
Peak input power running SpecJBB
AC Input Models
100 to 240 VAC,
50-60 Hz
At 100 VAC: 7.0A
At 200 VAC: 3.5A
At 100 VAC: 660.3 W
2253.0 BTU/hour
(2377.1 KJ/hour)
9.2 W
381.5 W
615.3 W
187.0 W
200.0 W
SPARC Enterprise T5120 and T5220 Servers Site Planning Guide
DC Input Models
-48 to -60 VDC
At -48 VDC: 15.4A
At -48 VDC: 616.8 W
2104.5 BTU/hour
(2220.3 KJ/hour)
8.6 W
356.4 W
574.7 W
174.7 W
186.8 W