A. Raise and Position ECU4
1. Position ECU4 directly in front of door, wall or ceiling area to be accessed.
2. Stand on one of two short sides of the ECU4 unit, and place foot on the foot pedal of end floor truss.
3. Grasp Outer Legs and simultaneously lift upward until left and right Height Adjustment Ratchet Pins engage
in the appropriate set of holes. They are spaced in one inch increments. Repeat step on the opposite end for a
one man deployment. They are spaced in one inch increments. (Fig.11-1)
4. From this position, lift ECU4 until foam str ips make contact with ceiling tile and slightly compress Upper
Folding Frame contacting the ceiling. Depress the handles in to eliminate mechanical actions of the hole
punches for easy nal adjustment to the ceiling. (Fig. II-2) Ensure that all four Height Adjustment Ratchet
Pins are engaged in their respective holes. Note: To ensure level engagement with ceiling, be sure
to position ECU4 so that same number of holes on Inner Legs are visible and that Upper Folding Frame is
flush against ceiling tile frame. There should be no visible gaps under foam. If two persons are deploying the
ECU4, complete steps 2-4 simultaneously from each end of the unit. (Fig. II-3)
5. If the doors to the ECU4 envelope are hanging very low, you may need to adjust the Velcro Cuffs
(Part B: Step 1, pg. 4; FIG. B-1) to a lower loop on the ECU4 envelope. This will pull up the envelope and
raise the doorway.
6. When adjusting height of envelope, ensure that bottom of wide doors on ECU4 are flush against
floor truss to prevent hazard when entering or exiting ECU4. (Fig. II-4)
X
(Fig. II-1)
(Fig. II-2)
B. Deploying a NAM for Class III Negative Pressure with ECU4
1. The ECU4 has two ports; a 12.5" duct port and a 3.5" utility port for power cord, hoses, etc.
interchangeable on either end of the unit. If you are using the ECU4 with a Mobile Platform, the Tow Cart is
an accessary that caddy's the NAM attached to the platform. (Figs. II-5)
2. To attach the HEPA negative air machine, remove the internal Velcro seal and insert ex duct into the port.
(FIG. II-6)
3. Tighten the draw strings to seal port around the NAM ex duct to ensure a tight seal. (FIGs. II-7)
4. Open pressure relief vents, as needed, located inside envelope, beneath windows on both cargo
doors, and the non-Flange side door. Turn on HEPA-Filtered negative air machine on. As the
air pressure inside the unit lowers, the sides of the unit will begin to be drawn in.
X
(Figs. II-5)
www.mintie.com
(Fig. II-3)
(FIG. II-6)
1-800-9MINTIE
1-323-225-4111
Adjust envelope height by locating Velcro
X
loops above or below locking corner (shown
in the left hand of the person pictured left)
4-loops above in short ceilings, 1 above in
tall ceilings.
(Fig. II-4)
(FIGs. II-7)
This is
(FIG. II-8)