Original Issue Date: 9/09
Model: 40- -180EOZD/EOZC and 33- -150EFOZD/EFOZC
Market: Marine
Subject: Full Feature Panel Kits
Introduction
Installation of the Full Feature Panel kit allows generator
set starting/stopping from a location remote from the
generator set. The panel includes an illuminated DC
voltmeter,
engine
oil
temperature gauge, and hourmeter. See Figure 1 for kit
selection. Use these kits on generator sets equipped
with Decision-Makerr 3+ controllers. See Figure 2 for
panel features.
Note: The installation of the Full Feature Panel requires
the control wiring kit GM51368-KP1 (33--99 kW)
or
GM51368-KP2
customer provided. See Figure 18.
Generator Set
Model
40EOZD/EOZC,
33EFOZD/EFOZC
55/65EOZD/EOZC,
40/50EFOZD/EFOZC
80/99EOZD/EOZC,
70/80EFOZD/EFOZC
125EOZD/EOZC,
100EFOZD/EFOZC
150EOZD/EOZC,
125EFOZD/EFOZC
180EOZD/EOZC,
150EFOZD/EFOZC
Figure 1 Kit Selection
The DC voltmeter measures the voltage of the starting
battery(ies).
Check the battery manufacturer's
recommendation for correct operating voltage.
The engine oil pressure gauge measures the engine
oil pressure. Refer to the following instructions for
locating the oil pressure sender.
Note: During the engine break-in period, the engine
sometimes produces high oil pressure readings.
Consult the service manual for specific values.
INSTALLATION INSTRUCTIONS
pressure
gauge,
coolant
(100--180
kW)
unless
Voltage
Kit No.
12
GM51369-KP1
24
GM51369-KP2
12
GM51369-KP3
24
GM51369-KP4
12
GM51369-KP5
24
GM51369-KP6
12
GM51369-KP7
24
GM51369-KP8
12
GM51369-KP9
24
GM51369-KP10
12
GM51369-KP11
24
GM51369-KP12
1
10
9
8
1. Frequency meter
2. Voltmeter
3. Ammeter
4. Ammeter switch
5. On light
Figure 2 Panel Features
The coolant temperature gauge measures the engine
coolant temperature. Refer to the following instructions
for locating the coolant temperature sender.
The hourmeter records the total generator set
operating
hours
for
scheduling.
Note: For generator sets already in service, the
hourmeter
on
accumulated hours and, therefore, reflect a
different reading than the panel hourmeter. Use
the same hourmeter each time to schedule
maintenance.
TT-1501
9/12a
2
3
A-344404-T
7
6
6. Start/stop switch
7. Hourmeter
8. Volt gauge
9. Temperature gauge
10. Oil pressure gauge
reference
in
maintenance
the
controller
will
4
5
have