AQmatic NX48 Instrukcja serwisowa - Strona 8
Przeglądaj online lub pobierz pdf Instrukcja serwisowa dla Kontroler AQmatic NX48. AQmatic NX48 18 stron. Nxt stager controller
MASTER PROGRAMMING MODE FLOW
NOTE: Display will only appear on the master timer and it must be
CHART continued
programmed as valve position #1. Use the Shift button to move one space
to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 2:
gpm
2 to 998 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 3 or 4 to appear. Use
the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 3 or 4 to appear. Use
the Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP POINT 3:
gpm
3 to 999 gpm
1 to 3997 Lpm
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
TRIP DELAY 3:
30 SECONDS
NOTE: Display will only appear on the master timer and it must be
programmed as valve position #1. System size must be 4 to appear. Use the
Shift button to move one space to the left.
NOTE: This screen will only display for System 14.
REGENERATION DAY
OVERRIDE:OFF
REGENERATION DAY
OVERRIDE:01 DAYS
Options: Off (Default for Meter) or On (Default for Time Clock)
Range: 1 to 99 Days
REGENERATION
TIME:
02:00AM
Options: A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override
is on.
CYCLE 1 00:10:00
CYCLE 2 01:00:00
Options: 01:00:00 for Conditioner for the 48-00 Stager & 51-09 Stager (Default)
00:00:00 for Filter for the 48-00 Stager
CYCLE 3 00:10:00
CYCLE 4 OFF
CYCLE 4 00:12:00
NXT
Stager
Controller
CYCLE 5 OFF
Example:
Off (Default for Meter)
On (Default for Time Clock)
Example:
1 Day
Example:
2:00 A.M. (Default)
Example: Backwash
00:10:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
Example: Brine
01:00:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
Example: Fast Rinse
00:10:00 (Default 48-00 Stager & 51-09 Stager)
(Hours:Minutes:Seconds)
Example:
Off (Default 48-00 Stager)
Example: Refill
00:12:00 (Default 51-09 Stager)
(Hours:Minutes:Seconds)
AU11
Example:
Example:
Off (Default 51-09 Stager)
CYCLE 5 OFF
NOTE: This screen will only display when cycle 4 is not OFF.
Example:
AUXILIARY RELAY:
Auxiliary Relay is Disabled
DISABLED
Options: Enabled
Disabled (Default)
Example:
AUX RELAY OUTPUT
Auxiliary Relay Output Start 1 at
START 1 00:00:00
0 hours, 0 minutes, & 0 seconds
Range:
00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
Example:
AUX RELAY OUTPUT
Auxiliary Relay Output End 1 at
END 1 00:00:00
0 hours, 0 minutes, & 0 seconds
Range:
00:00:00 to 18:00:00
Example:
CHEMICAL PUMP:
Chemical Pump is Disabled
DISABLED
Options: Enabled
Disabled (Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
Example:
CPO AUX RELAY
Energize Chemical Pump relay every 50 gals (50)
VOLUME:
000 9
Energize Chemical Pump relay every 200 L (200)
Range:
1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
Example:
CPO AUX RELAY
Each time chemical pump relay is on, run for
TIME:
00:00:00
30 seconds (00:00:30)
Range:
00:00:00 to 02:00:00
Example:
FLOW METER:
1.0 Paddle Flow Meter
1.0 PADDLE
Options: 1.0 Paddle
1.0 Turbine
1.5 Paddle
1.5 Turbine
2.0 Paddle
3.0 Paddle
Generic
NOTE: Default flow meter type is based on the valve type. This screen will
only display on the lead unit for System Types 6 & 7. All other system types
it will display for all units.
Example:
MAXIMUM FLOW
Maximum Flow Rate of 0 gpm
RATE:
0000 gpm
Range:
20 - 2000 gpm (U.S. Format)
20 - 2000 Lpm (Metric Format)
NOTE: Only displayed if "Generic" is chosen for the flow meter.
Example:
ADD 01 GALLONS
Add 1 Gallon for Each Pulse in U.S. Format
EVERY 001 PULSES
Options: Gallons (U.S. Format)
Liters (Metric Format)
Range:
1 - 99 Gallons (U.S. Format)
0.1 - 09.9 L (Metric Format)
Pulses: 1 - 99
NOTE: Only displayed if "Generic" is chosen for the flow meter.
Example:
PROGRAMMING UNIT
Master Programming Mode is Exiting
PLEASE WAIT...