A.B.S. FIREKILL 15241 Dane techniczne

Przeglądaj online lub pobierz pdf Dane techniczne dla Gaśnica A.B.S. FIREKILL 15241. A.B.S. FIREKILL 15241 3 stron. 1-3-6-9-12 kg powder abc

Technical Bulletin
FIREKILL SYSTEMS 1-3-6-9-12 kg POWDER ABC
RINA APPROVED ISO 9094:2015 No. 525310CS/002- ISO 14520
Description:
FIREKILL is an automatic extinguishing system composed by a
pressurized cylinder filled with
It is equipped with manual remote control and equipped with a
thermosensitive bulb, at 93°C (or on request at 68°).
It must be equipped with pressure switch to check charge.
If the fire extinguisher is located inside the space protected or if
the activation of the fixed system is automatic, a visual indication
of discharge outside the protected room shall be provided.
The visual indication must be chosen by Customer
depending on the detection system specifications.
FIREKILL has a versatile valve, completely automatic without use
of any source of energy. It has a manual remote control pull cable
or on request a remote battery control electric box actuator.
Moreover it is possible to connect a control panel that controls the
smoke detectors.
FIREKILL unique valve has two outlet diam. 3/8" pipes, a maximum
of 4 nozzles, it may distribute the jet with precision in the effective
point of the fire risk.
Assembly without necessity to thread tubes,
extremely easy and quick. Suitable also to protect mixers of
varnishes, garages, flammable liquids storage, etc.
Extinguishing agent
Dry chemical powder ABC 30% is produced in according to EN
615 (1995) and ISO 9001 quality control.
The basic components of dry powder are ammonium phosphate
and ammonium sulphate with special silicones additives enabling
easy flow discharge and avoiding any checking process.
Dry powder is not corrosive, not abrasive, non toxic for humans
and animals.
Note: other kinds of powder may be used ABC 30% ask our
technical office for compatibility.
The kit includes following parts:
Steel cylinder CE;
Rapid discharge valve made of chromed brass M30x1,5 with
manometer and thermosensitive bulb at 93°C (5);
Extinguishing agent;
Pipe with fast connection couplings (3);
Discharge nozzles made of chromed brass (1);
Remote control with handle (4+2);
Electric actuator (6) (optional) which connects the remote
control to an automatic control panel;
Wall bracket (8);
Use:
(2)
1) Pull the handle
in case of fire or
2) (If installed) Push the button on the control box to activate the
pyro. actuator;
3) The temperature higher than sprinkler bulb temperature will
activate the FIREKILL.
Operation:
The unit is pressurized at 14 bar at 20°C.
Code
Charge Protected zone
kg
1
15241
15227
3
15228
6
15226
9
15229
12
On request it will be availabe also 2 and 4 kg
Lombardia Street 310, 20861 S.Dam. Brugherio
Tel. +39 - 039 - 839631 - Fax. +39 - 039 - 8396349
1370
EC certificate
POWDER
ABC.
Illustration 1
Q.ty nozzle
3
m
1.7
2
5.1
2
10
2
15
4
20
4
Technical data are subject to modification
for improvements without prior notice
a.b.s. S.r.l. (Milan) Italy
www.absfire.it
Capital euro 2,000,000.00
Installation (illustration 1)
The FIREKILL must be hanged to its metal wall bracket inside or
outside the protected area.
Check the pressure looking at the pressure gauge the needle
must be in green sector. Fix the pipes (3) from the FIREKILL body
to the area to be protected, connect the discharge nozzles (1) at
the end of the pipes (3), near the dangerous point or the
protected area.
Fix the remote control cable (4) to the hexagon (7) and to the
remote control handle (2).
Safety pin (5) must be pulled out at the end of all above
operations. Now the FIRE KILL is ready to work.
FIREKILL can be activated manually by pulling the remote control
handle (2), otherwise automatically when the bursting temperature
of Sprinkler bulb is reached.
Bulb glass can be supplied with bursting temperature at 93 or
68°C.
The electric actuator (6) can be supplied on request. It can be
connected with an emergency control push button or through a
control panel in case there is an automatic detection system.
A standard detection system for our firekill system is composed by:
Low pressure switch cod. 23024, which directly indicates
alarm leaks or discharging In case of need of the low pressure
switch, please inform the manufacturer before ordering, so we
can mount it before the pressurization process;
Control panel which enable the perfect control of the full system
cod. 23022 or 23022_1 or 23023;
Thermosensitive detectors, cables or candels.
The electric actuator is a pyrotechnical charge, 5 years guaranteed
at a work temperature from -20°C up to +80°C and humidity of
100%. The pyrotechnical charge can work with minimum 12 V
tension and 1 A current.
Electrical connection:
The electrical connection to the pyrotechnical actuator must be
made by a shielded wire; it must be connected directly from battery
to the emergency push-button (Control Box Cod. 23022, 23022_1
or 23023) and to the actuator. Avoid to connect the actuator in
different positions (like fuses panel) to avoid accidental activations.
Torque force:
The valve is screwed down to the tank at the prefixed torque
between 5 and 6 Kg/m (i.e. between 50 and 60 Nm).
2
Max pipe
length mt x 2
2
4
5
6
8
7
4
6
3
1
Mount only
in vertical position.
For horizontal or
upside
need, contact
factory when
ordering
Data Sheet
Code
Date
Check
15241
Fire Extinguisher
22/02/15
5
8
Rev
Pag.
JC
5
1/3
/AL