Aqua Control Inc. (ACI) is certified to manufacture UL Listed Industrial Control Panels (UL 508A), and all control panels are UL listed except 460V panels
or panels built with prior agreement for certain special configurations. Certain special configurations, the 1hp-115V, all 460V and all 575V control panels
cannot be UL Listed because of the National Electric Code and UL requirements.
(If an ACI control panel was ordered with your unit, the control panel instruction manual may be found inside the control panel enclosure.)
Control panels should always be installed in a manner that minimizes heat inside the panel since the panels generate some heat and they contain heat
sensitive components (motor overloads). Sunlight is the most significant source of heat, so the control panels should be installed out of direct sun as much
as possible. The door of the control panel, particularly, should not face south or west unless it is protected from sunlight.
Verify voltage at the rotary disconnect prior to start up. Each outer leg should be 120 volts to Neutral unless you have 460/480 volt 3-phase power.
If you have power with a hot leg e.g., 230 volt 3-phase power, that wire should be connected to the center lug of the rotary disconnect.
At installation and initial start up, it is recommended to record the actual voltage under load (while the unit is running) and the running amperage of the
unit. This can be kept inside the control panel for future reference. This allows for easy determination if something at site or with the installation has
changed. The correct voltage and amperage ratings are on the schematic and on the door label of the control panel.
Any Aqua Control, Inc. aerator can be operated continuously or intermittently as desired except during freezing weather. If a less than normal flow
is observed, it is imperative that the cause be promptly investigated and corrected. Failure to do so can cause cavitation resulting in pump and
motor damage and will void the warranty. Reduced flow will usually be due to a blockage and must be resolved.
CONTROL PANELS
INSTALLATION
LOCATION OF CONTROL PANELS
PRE-START UP
START UP
Aqua Control, Inc. 60 Hz. Select Series 2 Instruction Manual
9