5.4 System Setup Menu
System Setup
System Work Mode
Battery
Setting
Gen Port
Grid Setting
Use
Basic
Advanced
Device Info.
Setting
Function
5.5 Basic Setup Menu
Basic Setting
Time Syncs
Beep
Auto Dim
Year
Month
Day
Basic
Set
2019
03
17
Hour
Minute
24-Hour
09
15
Factory Reset
Lock out all changes
5.6 Battery Setup Menu
Battery Setting
Batt Mode
Lithium
400Ah
Batt Capacity
Batt
Mode
Use Batt V
Max A Charge
40A
Use Batt %
Max A Discharge
40A
No Batt
Activate Battery
This is System Setup page.
This is Basic Setup page.
Lithium Battery
Batt Mode-------- Lithium
Max A charge-------- 0-185A
Max A Discharge-----0-185A
Activate Battery------Enable
AGM Battery
Batt Mode-------- Use Batt V or Use Batt V%
Batt Capacity-------- 50-2000Ah
Max A charge-------- 0-185A
Max A Discharge-----0-185A
Activate Battery ------Enable
No Batt --- No need to set other parameters,
keep the default value.
- 25 -
Battery Setting
②
①
Start
30%
30%
Batt
A
40A
40A
Set2
Gen Charge
Grid Charge
Gen Signal
Grid Signal
Gen Max Run Time
0.0 hours
Gen Down Time
0.5 hours
Battery Setting
Lithium Mode
00
Batt
Set3
Shutdown
10%
Low Batt
30%
Restart
80%
This is Battery Setup page.
Start =30%---It indicates that the Generator will start when
the Battery capacity is less than 30% in the condition of
Off-grid mode.
A
= 40A---It indicates the Current that the Generator
charges the Battery after started.
Gen Charge---The Switch that the Generator charges the
Battery.
Gen Signal ---It indicates whether the Generator's ATS
signal is on.
Max RunTime(x.xhous)Indicates that the generator is the
longest in a day,The time x.xhours can be run, and the
generator will be turned off when the time is up.
24.0hours (default) means that It keeps running without
shutting down.
DownTime(x.xhours)It indicates the delay of the
Generator to shut down after it has reached the run time.
This is Grid Charge, you need select.
Start =30%---no use,for customization.
A
= 40A--- It indicates the Current that the Grid charges
the Battery.
Grid Charge---The Switch that the Generator charges the
Battery.
Grid Signal ---Disable.
Lithium Mode--This is BMS protocol.default is 0 please
reference the document(Approved Battery-Deye).
Shutdown 10%--the inverter will shutdown if the SOC is
below this.
Low Batt 20% --the inverter will shutdown if the SOC is
below this.
Restart 40%
--Restart level when inverter shutdown.