Deye SUN-5K-SG03LP1-EU Podręcznik użytkownika - Strona 15

Przeglądaj online lub pobierz pdf Podręcznik użytkownika dla Falownik Deye SUN-5K-SG03LP1-EU. Deye SUN-5K-SG03LP1-EU 19 stron. Hybrid inverter

Deye SUN-5K-SG03LP1-EU Podręcznik użytkownika

5.8 Grid Setup Menu

Grid Setting
Grid Mode
General Standard
UL1741
IEEE1547
Grid
CPUC RULE21
Set1
SRD-UL-1741
Grid Type
220V Single Phase
120/240V Split Phase
120/208V 3 Phase
120V Single Phase
Grid Setting
Grid Frequency
50HZ
60HZ
Grid
Set2
Reconnection Time
60S
PF
1.000
Grid HZ High
Grid Vol High
60.5Hz
265.0V
Grid HZ Low
Grid Vol Low
59.3Hz
185.0V
Grid Setting
Q(V)
FW
VW
Grid
V1:0.0V
Q1:0.00
Fstart:0.00Hz
Vstart:0.0V
Set3
V2:0.0V
Q2:0.00
Fstop:0.00Hz
Vstop:0.0V
Normal Ramp rate
V3:0.0V
Q3:0.00
0.0%/s
V4:0.0V
Q4:0.00
Soft Start Ramp rate
0.0%/s
Grid Setting
L/HVRT
L/HFRT
Grid
HV2:0.0V
0.16S
Set4
HV1:0.0V
0.16S
HF2:0.00HZ
0.16S
LV1:0.0V
0.16S
HF1:0.00HZ
0.16S
LV2:0.0V
0.16S
LF1:0.00HZ
0.16S
LV3:0.0V
0.16S
LF2:0.00HZ
0.16S
Please select the correct Grid Mode in your local area. If
you are not sure, please choose General Standard.
Please select the correct Grid Type in your local area,
otherwise the machine will not work or be damaged.
UL1741&IEEE1547,CPUC RULE21,SRD-UL-1741
No need to set the function of this interface.
General Standard
Please select the correct Grid Frequency in your local area.
You can hole this in default value。
For California only.
For California only.
- 25 -

5.9 Generator Port Use Setup Menu

GEN PORT USE
Mode
Generator Input
Gen connect to Grid input
PORT
Set1
SmartLoad Output
On Grid always on
Power
Open Delay
1000W
60Min
OFF
95%
Micro Inv Input
ON
100%
Ml export to Grid cutoff

5.10 Advanced Function Setup Menu

Advanced Function
Solar Arc Fault ON
Clear Arc_Fault
Func
Set1
System selfcheck
Gen peak-shaving
Power
7000W
Grid peak-shaving
Power
4000W
Advanced Function
DC1 for WindTurbine
DC2 for WindTurbine
Wind
V1
0V
0.0A
V7
0V
0.0A
Set2
V2
0V
0.0A
V8
0V
0.0A
V3
0V
0.0A
V9
0V
0.0A
V4
0V
0.0A
V10
0V
0.0A
V5
0V
0.0A
V11
0V
0.0A
V6
0V
0.0A
V12
0V
0.0A
Generator Input:use Generator
SmartLoad Output: if the SOC is up than
"ON"and solar power is high than 1000W.
the inverter will open smartload.
On Grid always on:mean when have Grid,the
smartload will always on
Micro Inv Input:Inverter will open
Microinverter.if the SOC is below the"ON"
and close if the SOC is up than the"OFF"
Solar Arc Fault ON---This is only for US.
System selfcheck ---Disable. this is only for factory.
Gen Peak-shaving---Enable When the power of the
generator exceeds the rated value of it, the inverter will
provide the redundant part to ensure that the generator
will not overload.
Grid Peak-shaving---Enable When the power of the grid
exceeds the set value, the inverter will provide the
redundant part to ensure that the grid power does not
exceed the set value.
This is for WindTurbine
- 26 -