Aqua Free FLUSH 2.0 Instrukcja obsługi i instalacji - Strona 6

Przeglądaj online lub pobierz pdf Instrukcja obsługi i instalacji dla Produkt hydrauliczny Aqua Free FLUSH 2.0. Aqua Free FLUSH 2.0 7 stron.

RUN TIME: Duration of flushing
Example: RUN TIME = 5': Flushing continues for 5 minutes.
Times can be increased with the "+" key.
Times can be reduced with the "-" key.
MANUAL: Mode for drawing water manually and
checking the functioning of the flushing system
(test flush)
The valve is opened by pressing the "+" key.
The valve is closed by pressing the "-" key.
10
9
Trouble Shooting
The following table provides typical error modes an sesolu-
tion for the FLUSH 2.0 unit. If your error is not listed please
contact your local Aqua free representative.
Error
Cause
Flushing
Water supply
programme
faulty
does not run
The flushing
program has not
been saved
The battery is flat
(the "DELAY",
"FREQUENCY"
and "RUN TIME"
LEDs are
flashing)
Level switch
incorrectly fitted
Level switch
Washbasin is not
comes away
clean
from side of
washbasin
Suction cup is not
clean
Leakage
Faulty sealing
between water
gasket
outlet and
FLUSH unit
Procedure
Check that the tap
and any isolation
valves are open
Press SET key for
5 seconds
Change the battery
Check that the
level switch can
move freely and
the float is pointing
downwards
Check that the
surface of the
washbasin is
clean, dry and free
of grease
Check that the
surface of the
suction cup is
clean, dry and free
of grease
Check the sealing
gaskets and
replace any that
are damaged
11