Hardware Specifications – IEC
Interfaces:
2 RJ-45 RS-232 serial ports (9,600 8-N-1)
10 or 20 IEC 320-C13 outlets
Power:
PM10i-10A
100–240 VAC, 10 A, IEC 320-C14 inlet
10 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM10i-15A*
100–240 VAC, 15 A, IEC 320-C14 inlet
15 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM10i-16A
100–240 VAC, 16 A, IEC 320-C20 inlet
16 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM10i-20A,* PM20i-20A*
100–240 VAC, 20 A, IEC 320-C20 inlet
20 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM10i-L30A,* PM20i-L30A*
100–240 VAC, 30 A, NEMA L6-30P twist-lock plug
30 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
Operating
Temperature:
50ºF to 122ºF (10ºC to 50ºC)
Storage
Temperature:
–40ºF to 185ºF (–40ºC to 85ºC)
Humidity:
5% to 95% noncondensing
Dimensions:
(W x D x H)
PM10i-10A, -15A, -16A, -20A
17 x 8 x 1.75 in. (43.18 x 20.32 x 4.45 cm)
PM10i-L30A, -32A, -32Au
17 x 12 x 1.75 in. (43.18 x 30.48 x 4.45 cm)
PM20i-16A, -20A, -L30A, -32A, -32Au
2 x 2.8 x 66 in. (5.08 x 7.11 x 167.64 cm)
Weight:
PM10i
11.1 lb
5.0 kg
PM20i
14.1 lb
6.4 kg
Certifications:
FCC Part 15, A
EN55022, A (CE)
EN60950
*Units are certified to 80% of max. current rating.
International models.
Part Number
Model
Description
ATP3110
PM10i-10A
10 outlets, 10 A max. branch, IEC 320-C14
ATP3115-001
PM10i-15A
10 outlets, 15 A max. branch, IEC 320-C14
ATP3116
PM10i-16A
10 outlets, 16 A max. branch, IEC 320-C20
ATP3120-001
PM10i-20A
10 outlets, 20 A max. branch, IEC 320-C20
ATP3231-001
PM10i-L30A
10 outlets, 30 A max. branch, NEMA L6-30P
ATP3230
PM10i-32A
10 outlets, 32 A max. branch, IEC 309
ATP3232
PM10i-32Au
10 outlets, 32 A max. branch, unterminated
ATP2116
PM20i-16A
20 outlets, 16 A max. branch, IEC 320-C20
ATP2120-001
PM20i-20A
20 outlets, 20 A max. branch, IEC 320-C20
ATP3130-001
PM20i-L30A
20 outlets, 30 A max. branch, NEMA L6-30P
ATP2132
PM20i-32A
20 outlets, 32 A max. branch, IEC 309
ATP2131
PM20i-32Au
20 outlets, 32 A max. branch, unterminated
CAB0055
PM10i, 10 A Power Cable
CAB0087
PM10i, 10 A Power Cable
CAB0088
PM10i, 10 A Power Cable
CAB0089
PM10i, 10 A Power Cable
CAB0191
PM10i, 15 A Power Cable
CAB0192
PM10i, PM20i, 16 A Power Cable
CAB0193
PM10i, PM20i, 16 A Power Cable
CAB0194
PM10i, PM20i, 16 A Power Cable
CAB0195
PM10i, PM20i, 20 A US Power Cable
CAB0197
PM10i, PM20i, 20 A US Power Cable
CAB0198
PM10i, PM20i, 20 A US Power Cable
PM10i-32A, PM20i-32A
100–240 VAC, 32 A, IEC 309 plug
32 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM10i-32Au, PM20i-32Au
100–240 VAC, 32 A, unterminated cable
32 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
PM20i-16A
100–240 VAC, 16 A, IEC 320-C20 inlet
16 A max. branch circuit rating
10 A max. per IEC 320-C13 outlet
CSA (fully compliant to UL standard)
EN55024
C-Tick
8 ft, IEC320-C13 to AS3112, AUS & NZ
8 ft, IEC320-C13 to CEE 7/7 Schuko,
Continental EU
8 ft, IEC320-C13 to BS1363, UK &
Ireland
8 ft, IEC320-C13 to NEMA 5-15P, USA
8 ft, IEC320-C13 to NEMA 6-15P, USA
8 ft, IEC320-C19 to AS3112,
AUS & NZ
8 ft, IEC320-C19 to CEE 7/7
Schuko, Continental EU
8 ft, IEC320-C19 to BS1363,
UK & Ireland
8 ft, IEC320-C19 to NEMA
5-20P, USA
8 ft, IEC320-C19 to NEMA
L6-20P, USA
8 ft, IEC320-C19 to NEMA
L5-20P, USA
Corporate Headquarters
4991 Corporate Drive, Huntsville, AL 35805
TEL 866.277.1924 FAX 256.430.4030
www.avocent.com
Features
Connectivity
RS-232 serial port for configuration and management
Second RS-232 serial port for control-level daisy chaining
(up to 128 outlets)
Full RS-232 signal support allows dial-in access via modem
Administration
Name assignment per IPDU (up to 8 characters)
Name assignment per outlet (up to 16 characters)
Local authentication support (up to 8 users)
Per-outlet access control lists
Management
Independent control of power outlets (power on/off, cycle)
Virtual lock per outlet (on or off states)
Sequential power up with user-defined inter-outlet delays
Global, true RMS current monitoring per IPDU
Two-digit 7-segment LED current display
On/off status LED per outlet
User-defined overcurrent threshold with alarm
Built-in visual and audible alarms
Built-in ambient temperature sensor
Form Factors
Industry's highest outlet density (up to 10 outlets per 1U)
Horizontal (1U) and vertical (0U) models address a wide variety
of applications
Integration Features*
Integrated power management through console and KVM sessions
CLI, menu and GUI interfaces
Multioutlet grouping for devices with redundant power supplies
RADIUS, TACACS+, Kerberos, LDAP, and Active Directory
server-based authentication with local fallback
Token-based strong authentication (RSA SecurID)
Event logging via syslog
Fault notification via e-mail, SMS page, SNMP trap
SNMP integration with enterprise systems
*Features available when product is used in conjunction with Cyclades ACS console servers, DSR
switches, Cyclades OnSite branch office appliance or DSView 3 management software (not included).
IEC
Inputs
NEMA L6-30P
on fixed 8 ft power cord
on fixed 8 ft power cord
Outlets
IEC 320-C13
Avocent, the Avocent logo, The Power of Being There, Cyclades, DSR
and DSView are registered trademarks of Avocent Corporation or its
affiliates. All other marks are the property of their respective owners.
Copyright © 2006. Avocent Corporation. All rights reserved.
1206-PMIEC-DS
Unterminated
IEC-309
on fixed 8 ft power cord
IEC 320-C14
IEC 320-C20
modular inlet
modular inlet