Allied ML14XP1-060 Instrukcja instalacji - Strona 12

Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Pompa ciepła Allied ML14XP1-060. Allied ML14XP1-060 17 stron. Split system heat pump r410a refrigerant

Torque Requirements
When servicing or repairing heating, ventilating and air
conditioning components, ensure the fasteners are appro-
priately tightened. Table 2 lists torque values for fasteners.
TABLE 2
TORQUE REQUIREMENTS
Parts
Service valve cap
Sheet-metal screws
Machine screws #10
Compressor bolts
Gauge port seal cap
IMPORTANT
To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.
Using Manifold Gauge Set
When checking the system charge, only use a manifold
gauge set that features low loss anti-blow back fittings.
Manifold gauge set used with HFC-410A refrigerant sys-
tems must be capable of handling the higher system oper-
ating pressures. The gauges should be rated for use with
pressures of 0 - 800 psig on the high side and a low side
of 30" vacuum to 250 psig with dampened speed to 500
psi. Gauge hoses must be rated for use at up to 800 psig
of pressure with a 4000 psig burst rating.
OPERATING BALL-TYPE SERVICE VALVE
1 - Remove stem cap with an appropriately sized wrench.
2 - Use an appropriately sized wrench to open. To open valve, rotate
stem counterclockwise 90°. To close, rotate stem clockwise 90°.
TO OPEN, ROTATE STEM
COUNTERCLOCKWISE 90°.
TO CLOSE, ROTATE STEM
CLOCKWISE 90°.
SERVICE PORT
SERVICE PORT
CORE
SERVICE PORT
CAP
FIGURE 12
Recommended Torque
8 ft.-lb.
11 NM
16 in.-lb.
2 NM
28 in.-lb.
3 NM
90 in.-lb.
10 NM
8 ft.-lb.
11 NM
BALL (SHOWN
CLOSED)
STEM CAP
OPERATING ANGLE-TYPE SERVICE VALVE
1 - Remove stem cap with an appropriately sized wrench.
2 - Use a service wrench with a hex-head extension (3/16" for liquid
line valve sizes and 5/16" for vapor line valve sizes) to back the
stem out counterclockwise as far as it will go.
When service valve is OPEN, the service port is
When service valve is CLOSED, the service port is
NOTE - A label with specific torque requirements may be affixed to
the stem cap. If the label is present, use the specified torque.
A service port cap protects the service port core from contamination
and serves as the primary leak seal.
1 - Remove service port cap with an appropriately sized wrench.
2 - Connect gauge set to service port.
3 - When testing is completed, replace service port cap and tighten
as follows:
With torque wrench, finger tighten and torque
cap per table 2.
Without torque wrench, finger tighten and
VALVE
use an appropriately sized wrench to turn
STEM
an additional 1/6 turn clockwise.
Reinstall Stem Cap
Stem cap protects the valve stem from damage and serves as the
primary seal. Replace the stem cap and tighten as follows:
With torque wrench, finger tighten and
then torque cap per table 2.
Without torque wrench, fi
en and use an appropriately sized
wrench to turn an additional 1/12
turn clockwise.
Page 12
SERVICE PORT CAP
SERVICE PORT CORE
(VALVE STEM SHOWN OPEN)
INSERT HEX WRENCH HERE
STEM CAP
ANGLE-TYPE SERVICE VALVE
(BACK-SEATED OPENED)
open to line set, indoor and outdoor unit.
(VALVE STEM SHOWN CLOSED)
INSERT HEX WRENCH HERE
ANGLE-TYPE SERVICE VALVE
(FRONT-SEATED CLOSED)
open to the line set and indoor unit.
FIGURE 13
ACCESS SERVICE PORT
FIGURE 14
1/6 TURN
11 12
1
2
10
9
3
4
8
5
7
6
1/12 TURN
11 12
1
2
10
9
3
4
8
7
5
6