Installation Guide - GreaseShield
0
GS1850 Unit: Ensure that there is sufficient clearance above and to the right of the unit for servicing
8
purposes (5.9"/150mm minimum).
Inlet Pipe - 1½"/40mm: To be piped with a sufficient fall of no less than 1 in 40.
Outlet Pipe - 2"/54mm: To be piped with a sufficient fall of no less than 1 in 40.
0
Invert Inlet - 1¼"/32mm: Must be kept capped off with the 1¼"/32mm FlexiPlumb Endcap provided (for servicing use only)
0
Decant Outlet Hose - ¾"/18mm: To be piped directly into the main drainage pipe via a vented drainage stack as shown.
The Hose must be fixed in place using the drainage hose support provided.
Pre-Filter: Ensure sufficient height above the Pre-Filter to allow for removal and daily maintenance of Pre-Filter basket.
Pre-Filter Basket: A Pre-Filter basket must be installed into the pre-filter at all times.
Pre-Filter Support Bar: The support bar must be installed when attaching the Pre-Filter
Vortex Flow Controller: Must be fitted to the Pre-Filter inlet connection.
Sampling Point: Connected to the outlet of the unit: it is essential in the analysis of effluent leaving the unit.
Running Trap: The outlet of unit must be fitted with a running trap to reduce foul smells.
FOG Container: Ensure that the container is not restricted or blocked for daily maintenance.
Hot Water Solenoid Valve: Hot water must be connected to the unit using the ¾" BSP (F/F} Red PVC Hose provided, water
supply must not exceed 3 bar pressure and 60
used. Mains water connections must be made via a WRAS approved isolation valve which follows a WRAS approved double
check valve.
Power Lead: The unit must be plugged into a 13 amp rated IP56 socket located below counter level.
Interconnecting Pipework: All pipework must be clipped and properly supported.
Stainless Steel Hygiene Stand (Optional Extra): GS1850 unit should be installed on a Stainless Steel Hygiene stand. It can
be adjusted up to 2"/50mm in height to allow the unit to be levelled on uneven surfaces and provide access for cleaning.